33
Gas Furnace
Gas Valve Relay Fault
If the control senses the gas valve as energized for more than one second when the control
is not attempting to energize the gas valve, or the gas valve is sensed as not energized
when it is supposed to be energized, then the control will lock out with the green LED off.
The control assumes either the contacts of the relay driving the gas valve have welded shut
or the sensing circuit has failed. The venter motor is forced off to open the pressure switch
to stop gas flow unless a flame is present. If the gas valve was sensed as closed when it
should be open and has not de-engerized after the ventor motor was shutoff for 15
seconds, then the ventor motor is re-energized to vent the unburned gas.
Flame Sensor
The flame sensor is a safety that proves when a flame is present while the gas valve is open
and in operation.
For Non-Condensing Models the flame sensor is located on top of the burner assembly with
(1) 1/4" screw.
For Condensing Models the flame sensor is located underneath the burner assembly with
(1) 1/4" screw.
Содержание CPG41838-U
Страница 2: ...2...
Страница 5: ...5 Unit Dimensions Original R22 with Gas Heat A B Series 43...
Страница 6: ...6 Original R22 with Electric Heat A B Series Unit Dimensions...
Страница 7: ...7 Unit Dimensions Original R410A with Gas Heat B C D E Series...
Страница 8: ...8 Unit Dimensions Original R410A with Electric Heat B C D E Series...
Страница 9: ...9 Unit Dimensions U Series R410A 80 Gas Heat...
Страница 10: ...10 Unit Dimensions U Series R410A up to 95 Gas Heat...
Страница 11: ...11 Unit Dimensions U Series R410A Electric Heat...
Страница 19: ...19 Gas Furnace 3 Remove the 11 screws 4 Remove the front furnace baffle...
Страница 46: ...46 Chassis Cooling Section...
Страница 79: ...79...