R
KEYPAD CONFIGURATION MODE
This section will focus on configuring the GEM-RP1CAe2/GEM-K1CA Keypads.
If there is more than one keypad in the system, we
recommend that either a GEM-RP1CAe2 or a GEM-K1CA keypad be used for programming.
KEYPAD INSTALLATION
Several types of keypads may be used with the GEM-P816:
the GEM-RP1CAe2/GEM-K1CA, the GEM-RP2ASe2/GEM-K2AS, the
GEM-RP3DGTL/GEM-K3DGTL, and the GEM-RP4RFC/GEM-K4RF series (see WI1182). Each must be assigned an address num-
ber (1–7) and each requires its own configuration procedure (see CONFIGURING THE KEYPADS, which follows, and DIRECT AD-
DRESS KEYPAD AREA OPTIONS).
At least 1 keypad must be used; only 1 is required for a single-area Commercial Burglary instal-
lation.
GEM-RP1CAe2/GEM-K1CA
- is a 2-line combination fire/burglary/access keypad capable of supporting 4 EZM zones and a
PGM output.
The GEM-RP1CAe2 or GEM-K1CA is recommended for programming. See "Important Note" on page 2
for more information regarding the buttons on the GEM-RP1CAe2/GEM-K1CA keypads.
CONFIGURING THE KEYPADS
A total of up to 7 keypads may be connected to the panel.
GEM-RP1CAe2/GEM-K1CA, GEM-RP2ASe2/GEM-K2AS, GEM-
RP3DGTL/GEM-K3DGTL, and GEM-RP4RFC/GEM-K4RF series keypads may be intermixed but require different configuration pro-
cedures, as described below and in WI1182.
Configuring the GEM-RP1CAe2/GEM-K1CA Keypad
Each GEM-RP1CAe2/GEM-K1CA keypad must be configured for (a) keypad tactile beep; (b) entry sounder; (c) keypad address; (d)
compatibility number; (e) EZM address; and (f) zone response.
To enter the Keypad Configuration Mode:
1. Move jumper JP1 (located in the center of the control panel board) from Pins 1-2 (top two) to Pins 2-3 (bottom
two).
NOTE:
See Wiring Diagram at the end of this manual.
2. After about 15 seconds, the display will read “
XX OUT OF SYSTEM
”, where XX indicates the keypad address.
3. Press
11123
R
and proceed as follows.
(Repeat the following procedure for all keypads).
Keypad Tactile Beep
Upon entering the Keypad Configuration Mode, “
KEYPAD BEEP ON
” will be displayed,
indicating that the tactile beep, which sounds when any button is pressed, is on.
To turn off the tactile beep, press the
U
button (the
U
button will toggle the tac-
tile beep on and off).
Press
R
to continue or press
C
to exit.
Entry Sounder
To turn off the keypad entry sounder during entry time, press
U
(the
U
button
will toggle the entry sounder on and off).
Press
R
to continue or press
C
to exit.
Keypad Address
If more than one keypad is installed, each must be assigned a unique keypad
address (that is, no two keypads may be numbered alike):
Keypads must be numbered consecutively (missing numbers are not permitted)
To assign the keypad number, proceed as follows:
1. Enter the assigned keypad number 01–07, then press
U
to save.
A valid
number will be acknowledged by a short beep; an invalid number will be re-
jected by a long beep.
2. Press
R
to continue or press
C
to exit.
Keypad Beep
ON
NORMAL
KEYPAD
CONFIGURE
Entry Sounder
ON
Keypad Address
01
Содержание Gemini GEM-P816
Страница 18: ...GEM P816 Programming Instructions Page 18 NAPCO Security Systems R THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 31: ...NAPCO Security Systems R GEM P816 Programming Instructions Page 31 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 32: ...GEM P816 Programming Instructions Page 32 NAPCO Security Systems R THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 33: ...NAPCO Security Systems R GEM P816 Programming Instructions Page 33 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 34: ...GEM P816 Programming Instructions Page 34 NAPCO Security Systems R THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 35: ...NAPCO Security Systems R GEM P816 Programming Instructions Page 35 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 45: ...NAPCO Security Systems R GEM P816 Programming Instructions Page 45 NOTES...