Chapter 6 Troubleshooting
Screw Compressor i-series
6-7
Symptom
Direct cause
Root cause
Action
10
Compressor
generates
abnormal
vibration
and/or
sound.
M rotor shaft
vibrates
excessively.
Rotor dynamic
balance is
disturbed.
If no other causes are found for
abnormal vibration, or if on-site
overhaul only has been repeatedly
performed for a long time, this
may be the cause.
→
Overhaul the compressor at a
place where a dynamic
balance
measurement/adjustment
system is available, such as
the MAYEKAWA Moriya
Factory.
Liquid flow-back
during startup
* Loud abnormal
noise at startup.
* If this is heard,
the compressor
may get damaged
instantaneously.
Refrigerant
liquefies and stays
inside upstream
piping when
equipment is
stopped.
There are many probable causes,
such as a leak inside liquid supply
solenoid valve on the load side,
insufficient heat exchange
(refrigerant evaporation) in heat
exchanger, or trapping due to
miss-piping in the piping line.
→
Identify the cause(s) and take
necessary measures. Then
overhaul and inspect the
compressor.
Liquid flow-back
during operation
* Notable frosting
on the suction
side.
* In many cases,
flow-back of mist
(steam) rather
than liquid occurs.
* Sometimes,
gas-liquid
separator
(accumulator) is
attached to
prevent this
symptom.
* See also the
causes in item 02,
"Insufficient
refrigerant flow".
Aperture of liquid
supply expansion
valve is large.
In case of temperature-type
expansion valve, check the
condition of temperature sensitive
cylinder and capillary tube. If any
defect is found, take necessary
actions.
If orifice gets unsuitable due to the
change in operating conditions,
replace the orifice.
In case of electronic expansion
valve, check devices attached on
the expansion valve aperture
control mechanism (circuit) such
as temperature sensor, converter,
controller (overheating regulator).
If any of them is found defective,
replace it.
In the same way as with
temperature-type expansion
valve, if orifice gets unsuitable due
to the change in operating
conditions, replace the orifice.
Expansion valve
aperture control
cannot keep up
with rapid change
in heat load on the
load side.
Avoid rapid change in heat load
that exceeds the set value of
follow-up range of "heat
exchanger on load side
(evaporator)" + "expansion valve".
For details, refer to the instruction
manuals related to devices/control
on load side.