Section 75
00-02-0522
04-06-11 -
10 -
a. Disabled
b. Enabled - Beeps with each keypress, sounds for errors. (Default).
9. Pressure Units
- User selection of display units.
a. PSI (Default)
b. kPa
c. bar
10. Temperature Units
- User selection of display units.
a. Fahrenheit (Default)
b. Celsius
11. Date Display
- Format Selectable.
a. American Style (Default)
b. European Style
12. Event Types
to record.
a. All events (Default)
b. Shutdown events only
13. Clear Event History
- Erases all stored history events.
14. Standby Mode Timer
- When the timer expires, the system goes into a lower power
standby mode. After it times out the LCD screen changes to a text message, the blue LCD
backlight is turned off, and the Energy Monitoring board is de-powered. Any keypress or a
remote call to run wakes the unit up. Value can be set between 30 seconds and 59 minutes 30
seconds or can be set to OFF.
15. Run to Destruct
- When run to destruct is enabled, the system will only sound alarms for
errors, instead of shutting down. Since this could lead to the destruction of the equipment or
the load, there is both a menu selection and a jumper that must be physically cut (see
schematic diagram), making this a deliberate choice.
a.
Disabled
(Default)
b.
Enabled
16. Edit Time and Date
- Allows user to
adjust