Dehumidifier ML420-MLT1400
Parameter
Description
Possible parameter selection
Default setting
01
Proportional band
1-15 % RH
5
02
Integration time
0-99 seconds
0 (= off)
03
Differential action, percentage
0-100 % RH
0 (= off)
04
Cycle time
0-999 seconds
20
05
Correction of the humidity sensors’s value
-15- +15 % RH
No settings
10
Offset, relay-2
0-20 % RH
10
11
Differential, relay-2
1-5 % RH
1
20
Minimum setpoint
0-100 % RH
0
21
Maximum setpoint
0-100 % RH
100
40
Delay in regaining supply after a power cut
0-99 min.
0
41
Forced solid-state output where sensor fault
0 = No; 1 = 100% output
0
42
Forced relay-2 output where sensor fault
0 = No; 1 = Yes
0
Table 1.2 Operator panel system parameters – VariDry