IceDry 800/1400
4
Installation
4.1 General
IceDry dehumidifiers are intended for installation in cold stores with ambient air down to minus 25 °C.
These conditions require that installation instructions are followed carefully as faulty installation can result
in serious operational disturbances.
If the unit is to be put into storage prior to installation, see section
.
4.2 Safety
W
W
WARNING!
ARNING!
ARNING!
The mains power supply is permanently connected to the main power switch of the unit. Adjustments,
maintenance and repairs must only be carried out by authorised personnel.
W
W
WARNING!
ARNING!
ARNING!
The wet air outlet is hot. To avoid burns from unintended contact, make sure it is insulated.
CA
CA
CAUTION!
UTION!
UTION!
The built-in heater requires a continuous power supply to prevent functional disorder. Only switch off the unit's
power in case of emergency.
CA
CA
CAUTION!
UTION!
UTION!
Condensation is easily formed on the inside of the duct due to the high humidity of the reactivation air. To avoid
condensation, the ductwork must be insulated
CA
CA
CAUTION!
UTION!
UTION!
Activate the main switch for the dehumidifier as soon as the unit has been installed. This allows the built-in heater
to operate and prevents internal ice formation.
CA
CA
CAUTION!
UTION!
UTION!
Before starting the unit, the reactivation air inlet and wet air outlet must be thoroughly checked. Any ice must be
removed. To avoid malfunction, it is important to have clear air passage throughout the ductwork.
CA
CA
CAUTION!
UTION!
UTION!
If the process airflow damper is fully open, the high cold air density in the cold-storage room could damage the
process air fan.
CA
CA
CAUTION!
UTION!
UTION!
Failure to correctly adjust the process and reactivation airflows could cause the unit to malfunction.
4.3 Site requirements
The dehumidifier is adapted to operation inside cold stores. The permitted operational temperatures
are from minus 25 to 0 °C. It is important that the intended installation site meets the location and space
6
Installation
190TGB-1037-G1307