Installation & owner's manual
When the lowest ambient temperature in the user’s region in
winter is within 0
℃
~10
℃
, the user may consider to use auxiliary
electric heater. Please refer to relevant professionals for the power
of auxiliary electric heater.
8.13 System antifreezing
In case of freezing at the water-side heat exchanger interval
channel, severe damage may be caused, i.e. heat exchange may
be broken and appears leakage. This damage of frost crack is not
within the warranty scope, so attention must be paid to antifreez-
ing.
1) If the unit that is shutdown for standby is placed in an environ-
ment where the outdoor temperature is lower than 0
℃
, the water
in the water system should be drained.
2) Water pipe may be frozen when the chilled water target flow
controller and anti-freezing temperature senor become ineffective
at running, therefore, the target flow controller must be connected
in accordance with the connection diagram.
3) Frost crack may happen to water-side heat exchanger at
maintenance when refrigerant is injected to the unit or is
discharged for repair. Pipe freezing is likely to happen any time
when the pressure of refrigerant is below 0.4Mpa. Therefore, the
water in the heat exchanger must be kept flowing or be thoroughly
discharged.
8.14 Wiring of
“
ON/OFF
”
weak electric port
First, corresponding parallel connect the “ON/OFF” port of
the
main unit’s electric control box,then, connect the “ON/OFF” signal
(provide by user) to the “ON/OFF” port of main unit as follows.
If the “ON/OFF” port is effective, the “Net on” icon of the wire
controller will be flashing.
First, corresponding parallel connect the “HEAT/COOL” port
of
the main unit’s electric control box,then, connect the
“ON/OFF” signal (provide by user) to the “HEAT/COOL” port
of main unit as follows.
0# electric control box
“ON/OFF” port
0# electric control box
“ON/OFF” port
0# electric control box
“ON/OFF” port
0# electric control box
“ON/OFF” port
Red
Blue
8.15 Wiring of
“
HEAT/COOL
”
weak electric port
Red
Blue
Brown
Black
Brown
Black
Connect the device provided by user to the “ALARM” ports of
the module units as follows.
If the unit is operating unnormally, the ALARM port is
closed,otherwise,the ALARM port is not closed.
8.16 Wiring of
“
ALARM
”
port
electric control box “ALARM” port
Red
Red
8.11 Disassembling compressor
Follow the following procedures if compressor needs to be
disassembled:
1) Cut off the power supply of unit.
2) Remove power source connection wire of compressor.
3) Remove suction and discharge pipes of compressor.
4) Remove fastening screw of compressor.
5) Move the compressor.
8.12 Auxiliary electric heater
When the ambient temperature is lower than 2
℃
, the heating
efficiency decreases with the decline of the outdoor temperature.
In order to make the air-cooled heat pump stably run in a relatively
cold region and supplement some heat lost due to de-frosting.
23
Modular Chiller MUEN-H6