6.3 Trial run
6.3.1 Start up the controller and check whether the unit displays a
fault code. If a fault occurs, remove the fault first, and start the
unit according to the operating method in the “unit control
instruction”, after determining that there is no fault existing in the
unit.
6.3.2 Conduct trial run for 30 min. When the influent and effluent
temperature becomes stabilized, adjust the water flow to nominal
value, to ensure normal operation of the unit.
6.3.3 After the unit is shut down, it should be put into operation 10
min later, to avoid frequent start-up of the unit. In the end, check
whether the unit meets the requirements according to the
contents in Table 9.1.
CAUTION
● The target flow controller must be installed correctly. The
wires of the target flow controller must be connected according
to electric control schematic diagram, or the faults caused by
water breaking while the unit is in operation should be the
user’s responsibility.
● Do not re-start the unit within 10 min after the unit is shut
down during trial run.
● When the unit is used frequently, do not cut off the power
supply after the unit is shut down; otherwise the compressor
cannot be heated, thus leading to its damages.
● If the unit is not in service for a long time, and the power
supply needs to be cut off, the unit should be connected to the
power supply 12 hours prior to re-starting of the unit, to
pre-heat the compressor.
7. USE
● The unit can control start-up and shut-down of the unit, so
when the water system is flushed, the operation of the pump
should not be controlled by the unit.
● Do not start up the unit before draining the water system
completely.
7.1 Use conditions of the unit
Fig.7-1
14
13
3
1
2
4
16
11
15
5
6
7
8
9
10
11
12
4
1. Operation icon
2. Mode area
3. Setting temperature
4. Timing On/Off
5. Function Icon
6. On-line Unit Qty. Indication
7. Reserved
8. Clock
9. Water temp.
10.ON/OFF Key
11.Right, Left Right Key
12.OK key
13. Setting key
14. Add, Reduce key
15. Cancel key
16. Reserved
. key
(Press for 3sec to
cancel timer)
(Press for 3sec to
unlock)
AUXILIARY
Installation & owner's manual
17
Modular Chiller MUEN-H6