OPERATION & PERFORMANCE
a. The standard voltage of power supply is 380-415V 3N~50Hz, the minimum allowable voltage is 342V, and the maximum voltage is
456V.
b. To maintain better performance, please operate the unit under the following outdoor temperature:
Performance characteristics of the unit
Use conditions of the unit
The air-cooled heat pump modular unit is composed of one or more modules. Each module has its own independent electric
control unit, and the electric control units of modules conduct information exchange through communication network. The
air-cooled heat pump modular unit is characteristics of compact structure and easy transportation and lifting, and in the meanwhile,
it also saves facilities, including cooling tower, cooling pump, and so on, for the user, and reduces installation cost.
The units provide central air handling devices or terminal equipment with chilled water or hot water. The unit is a completely
independent entirety type one, which is designed to be installed outdoors (on the ground or the roof). Each unit includes such main
parts as high-efficient and low-noise scroll compressor, air-cooled condenser, shell and tube (or plate) evaporator, micro-computer
control center, and so on. These parts are installed on steel structure base, so they are sound and durable.
The unit applies Chinese micro-computer control system, which can automatically conduct energy control according to the
magnitude of load, to achieve optimal matching and thus actually realizing optimal energy-saving operation. The product is
modularized unit, and parallel connection of 16 modules can be realized at most, so the user can adopt module combination
according his own demands. The product can be widely applied in air-conditioning engineering of various newly-built and rebuilt
industrial and civil buildings, such as restaurant, hotel, apartment, office building, hospital, industrial plant, and so on. The
air-cooled heat pump modular unit is the best choice for the place which has high requirement in noise and ambient environment
and which is short of water.
Operating range under cooling mode
Operating range under heating mode
-10
°
C~46
°
C
-10
°
C~21
°
C
c. The unit is of outlet water temperature control mode
outlet water temperature control
—
cooling: minimum temperature 5
°
C
, maximum temperature 17
°
C
; heating: minimum tempera-
ture
°
C
, maximum temperature 50
°
C
.
Cooling low water temperature
(
Unit:
℃)
Ambient
temperature
Outlet water
temperature
Cooling operating range
46
-10
Heating low water temperature
(
Unit:
℃)
Ambient
temperature
Outlet water
temperature
Heating operating range
21
Low water outlet temperature control—cooling: minimum temperature 0
℃
, maximum temperature 17
℃
(under this using condition,
the system must be added antifreeze agent); heating: minimum temperature 22
℃
, maximum temperature 50
℃
.
40
To activate low water outlet temperature control should be set the micro-switches on the
main PCB (see settings on page 13 of this manual).