10.3.3.9 Current protection of compressor (ODU P3/PC 08)
Outdoor unit zero speed protection(ODU PC44)
Compressor speed has been out of control(ODU PC46)
Compressor overcurrent failure(ODU PC49)
Current protection of compressor
Judge 1: Check whether the
input current of the power
supply wire is higher than max
protection current value
Yes
Replace the electric control box
Check whether
the refrigerant
system is ok
Judge 2: Check whether the
outdoor ambient
temperature is higher than
50
đ
No
Stop the unit
Yes
Judge 3: Check whether the
outdoor unit is bad ventilation
No
Make the outdoor unit ventilate well
Yes
Judge 5: The refrigerant
pipe is blocked
No
Let the refrigerant out, then use the high
pressure nitrogen or refrigerant to blow pipe,
vacuumize and charge the refrigerant again
Yes
Judge 4: Check whether the
heat exchanger is dirty
No
Clean the heat exchanger
Yes
Yes
Replace outdoor main
board,and check whether
the system can run normally
No
Yes
Trouble is solved
Service manual
MUEX-
H11 series
58
Содержание H11 Series
Страница 1: ...Service manual www mundoclima com CL21400 CL21407 MULTI INVERTER SERIE H11 R32...
Страница 11: ...10 MUEX 21 H11 3 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 12: ...11 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 13: ...12 MUEX 36 H11 4 Service manual MUEX H11 series...
Страница 14: ...13 MUEX 42 H11 5 Service manual MUEX H11 series...
Страница 41: ...EC 50 Open or short circuit of outdoor unit temperature sensor T3 T4 T5 Service manual MUEX H11 series 40...
Страница 73: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...