31
43
Average value of T2
(Sum T2 value of all indoor units)/(number of indoor units in good
connection)
44
Outdoor unit fan motor state
Off: 0, Super high speed:1, High speed:2, Med speed: 3, Low speed: 4,
Breeze:5, Super breeze: 6
45
The last error or protection code
00 means no malfunction and protection
46
F indoor unit capacity
47
F indoor unit capacity demand code
48
F indoor unit evaporator outlet temperature
(T
2B
F)
If the temperature is lower than -9
!
, the digital display shows “-9.” If the
temperature is higher than 70
!
, the digital display shows “70.” If the indoor
unit is not connected, the digital display shows: “――”
49
F indoor unit room temperature (T
1
F)
50
F indoor unit evaporator temperature (T
2
F)
51
EXV open angle for F indoor unit
52
Type of machine A
1:ATW; 0:Air conditioner
53
Water inlet temperature of heat exchanger
(TW_in)
If the temperature is lower than -9
!
, the digital display shows “-9.” If the
temperature is higher than 70
!
, the digital display shows “70.” If the indoor
unit is not connected, the digital display shows: “――”
54
Water outlet temperature of heat exchanger
(TW_out)
55
Water outlet temperature(TW1)
56
Gas pipe temperature(TR_out)
57
Liquid pipe temperature(TR_in)
58
Water temperature of the water tank(Tk)
59
Backwater
temperature
of
the
water
Tank(TWH)
60
Total outlet temperature of hydraulic module
system (after expansion tank)(TW1B)
61
Indoor unit status
Bit7
Reserve
The
display
value
is
a
decimalism
number.
For
example, the digital display
show 07, then Bit2=1, Bit1=1,
and Bit0=1.
Bit6
Reserve
Bit5
Reserve
Bit4
Reserve
Bit3
Reserve
Bit2
Protection from falling off of water
inlet and outlet temperature
sensor
Bit1
Anti-freeze protection
Bit0
Water pump 1: On 0: Off
62
Running mode of ATW
1: Machine A is a ATW, displaying the running mode sent by machine A
2: Machine A is not ATW, and it displays "--"
63
Setting temperature after
correct
(TD)
64
Setting temperature by controller(TS)
65
Setting temperature after water tank (TksD)
Machine A is not ATW, and it displays "--"
66
Setting temperature(Tks)
Machine A is not ATW, and it displays "--"
For other models,
Number
of
Presses
Display
Remark
0
Normal display
Displays running frequency, running state, or malfunction code
1
Quantity of indoor units with working connection
Actual data
Display
Number of indoor unit
1
1
2
2
3
3
4
4
2
Outdoor unit running mode code
Off: 0,Fan only: 1, Cooling: 2, Heating: 3, Forced cooling: 4. Forced
defrosting :A, DHW:C, Heating and DHW: d
Service manual
MUEX-
H11 series
Содержание H11 Series
Страница 1: ...Service manual www mundoclima com CL21400 CL21407 MULTI INVERTER SERIE H11 R32...
Страница 11: ...10 MUEX 21 H11 3 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 12: ...11 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 13: ...12 MUEX 36 H11 4 Service manual MUEX H11 series...
Страница 14: ...13 MUEX 42 H11 5 Service manual MUEX H11 series...
Страница 41: ...EC 50 Open or short circuit of outdoor unit temperature sensor T3 T4 T5 Service manual MUEX H11 series 40...
Страница 73: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...