32
3
Indoor unit A capacity
The capacity unit is horse power. If the indoor unit is not connected, the
digital display shows the following: “――”
(9K:1HP,12K:1.2HP,18K:1.5HP)
4
Indoor unit B capacity
5
Indoor unit C capacity
6
Indoor unit D capacity
7
Indoor unit E capacity
8
Indoor unit A capacity demand code
Norm code*HP
(9K: 1HP,12K: 1.2HP,18K: 1.5HP)
9
Indoor unit B capacity demand code
10
Indoor unit C capacity demand code
11
Indoor unit D capacity demand code
12
Indoor unit E capacity demand code
13
Outdoor unit amendatory capacity demand code
14
The frequency corresponding to the total indoor
units' amendatory capacity demand
15
The frequency after the frequency limit
16
The frequency sending to compressor control
chip
17
Indoor unit A evaporator outlet temperature
(T
2B
A)
If the temperature is lower than -9
ć
, the digital display shows “-9.” If
the temperature is higher than 70
ć
, the digital display shows “70.” If
the indoor unit is not connected, the digital display shows: “――”
18
Indoor unit B evaporator outlet temperature
(T
2B
B)
19
Indoor unit C evaporator outlet temperature
(T
2B
C)
20
Indoor unit D evaporator outlet temperature
(T
2B
D)
21
Indoor unit E evaporator outlet temperature
(T
2B
E)
22
Indoor unit A room temperature (T
1
A)
If the temperature is lower than 0
!
, the digital display shows “0.” If the
temperature is higher than 50
!
, the digital display shows “50.” If the
indoor unit is not connected, the digital display shows: “――”
23
Indoor unit B room temperature (T
1
B)
24
Indoor unit C room temperature (T
1
C)
25
Indoor unit D room temperature (T
1
D)
26
Indoor unit E room temperature (T
1
E)
27
Indoor unit A evaporator temperature (T
2
A)
If the temperature is lower than -9
!
, the digital display shows “-9.” If the
temperature is higher than 70
!
, the digital display shows “70.” If the
indoor unit is not connected, the digital display shows: “――”
28
Indoor unit B evaporator temperature (T
2
B)
29
Indoor unit C evaporator temperature (T
2
C)
30
Indoor unit D evaporator temperature (T
2
D)
31
Indoor unit E evaporator temperature (T
2
E)
32
Condenser pipe temperature (T3)
33
Outdoor ambient temperature (T4)
34
Compressor discharge temperature (TP)
The display value is between 30–129
!
. If the temperature is lower than
30
!
, the digital display shows “30.” If the temperature is higher than
99
!
, the digital display shows single and double digits. For example, if
the digital display shows “0.5", the compressor discharge temperature is
105
!
.
35
AD value of current
The display value is a hex number.
For example, the digital display tube shows “Cd”, it means AD value is
205.
36
AD value of voltage
37
EXV open angle for A indoor unit
Actual data/4.
If the value is higher than 99, the digital display shows single and double
digits.
For example, if the digital display shows “2.0", the EXV open angle is
120×4=480p.
38
EXV open angle for B indoor unit
39
EXV open angle for C indoor unit
40
EXV open angle for D indoor unit
41
EXV open angle for E indoor unit
42
Frequency limit symbol
Bit7
Frequency limit caused by IGBT
radiator
The
display
value
is
a
hexidecimal
number.
For
example,
the
digital
display
show 2A, then
Bit6
Frequency limit caused by PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Service manual
MUEX-
H11 series
Содержание H11 Series
Страница 1: ...Service manual www mundoclima com CL21400 CL21407 MULTI INVERTER SERIE H11 R32...
Страница 11: ...10 MUEX 21 H11 3 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 12: ...11 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 13: ...12 MUEX 36 H11 4 Service manual MUEX H11 series...
Страница 14: ...13 MUEX 42 H11 5 Service manual MUEX H11 series...
Страница 41: ...EC 50 Open or short circuit of outdoor unit temperature sensor T3 T4 T5 Service manual MUEX H11 series 40...
Страница 73: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...