18
8.
Installation Details
8.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm
N.cm
N.cm
Ф6.35
1500(153kgf.cm)
1600(163kgf.cm)
Ф9.52
2500(255kgf.cm)
2600(265kgf.cm)
Ф12.7
3500(357kgf.cm)
3600(367kgf.cm)
8.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-sectional area (mm²)
>3 and ≤6
0.75
>6 and ≤10
1
>10 and ≤16
1.5
>16 and ≤25
2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the
nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the
cable, fuse and switch.
8.3 Pipe length and the elevation
Maximum piping length and height difference
1 drive 2
1 drive 3
1 drive 4
1 drive 5
Max. length for all rooms (m)
40
60
80
80
Max. length for one IU (m)
25
30
35
35
Max. height difference between IU and OU (m)
15
15
15
15
Max. height difference between IUs (m)
10
10
10
10
Additional refrigerant charge
Connective Pipe Length(m)
Additional refrigerant
Liquid Side
Ø 6.35 (1/4”)
Ø 9.52 (3/8”)
Pre-charge pipe length (ft/m)
(pre-charge pipe length xN )
N/A
More than (pre-charge pipe lengthxN) ft/m
(Total pipe length - pre-charge pipe
lengthxN) x12g/m
(Total pipe length - pre-charge pipe
lengthxN) x24g/m
(Total pipe length - pre-charge pipe
lengthxN) x0.13oZ/ft
(Total pipe length - pre-charge pipe
lengthxN) x0.26oZ/ft
Caution:
Ș
Refrigerant pipe diameter is different according to indoor unit to be connected. When using the
extension pipe, refer to the tables below.
Service manual
MUEX-
H11 series
Содержание H11 Series
Страница 1: ...Service manual www mundoclima com CL21400 CL21407 MULTI INVERTER SERIE H11 R32...
Страница 11: ...10 MUEX 21 H11 3 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 12: ...11 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 13: ...12 MUEX 36 H11 4 Service manual MUEX H11 series...
Страница 14: ...13 MUEX 42 H11 5 Service manual MUEX H11 series...
Страница 41: ...EC 50 Open or short circuit of outdoor unit temperature sensor T3 T4 T5 Service manual MUEX H11 series 40...
Страница 73: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...