![mundoclima H11 Series Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/mundoclima/h11-series/h11-series_service-manual_1856790029.webp)
28
9.4 Outdoor unit point check function
A check switch is included on the outdoor PCB.
Push SW1 to check the unit's status while running. The digital display shows the following codes each time
the SW1 is pushed.
For
MUEX-21-H11.3 , MUEX-27-H11.3
Number
of
Presses
Display
Remark
0
Normal display
Displays running frequency, running state, or malfunction code
1
Quantity of indoor units with working connection
Actual data
Display
Number of indoor unit
1
1
2
2
3
3
4
4
5
5
2
Outdoor unit running mode code
Off: 0,Fan only: 1, Cooling: 2, Heating: 3, Forced cooling: 4. Forced
defrost:A
3
Indoor unit A capacity
The capacity unit is horse power. If the indoor unit is not connected, the
digital display shows the following: “――”
(9K:1HP,12K:1.2HP,18K:1.5HP,24K:2.0HP)
4
Indoor unit B capacity
5
Indoor unit C capacity
6
Indoor unit D capacity
7
Indoor unit E capacity
8
Indoor unit A capacity demand code
Norm code*HP
(9K: 1HP,12K: 1.2HP,18K: 1.5HP,24K:2.0HP)
9
Indoor unit B capacity demand code
10
Indoor unit C capacity demand code
11
Indoor unit D capacity demand code
12
Indoor unit E capacity demand code
13
Outdoor unit amendatory capacity demand code
14
The frequency corresponding to the total indoor
units' amendatory capacity demand
15
The frequency after the frequency limit
16
The frequency sending to compressor control
chip
17
Indoor unit A evaporator outlet temperature
(T
2B
A)
If the temperature is lower than -9
đ
, the digital display shows “-9.” If
the temperature is higher than 70
đ
, the digital display shows “70.” If
the indoor unit is not connected, the digital display shows: “――”
18
Indoor unit B evaporator outlet temperature
(T
2B
B)
19
Indoor unit C evaporator outlet temperature
(T
2B
C)
20
Indoor unit D evaporator outlet temperature
(T
2B
D)
21
Indoor unit E evaporator outlet temperature
(T
2B
E)
22
Indoor unit A room temperature (T
1
A)
If the temperature is lower than 0
!
, the digital display shows “0.” If the
temperature is higher than 50
!
, the digital display shows “50.” If the
indoor unit is not connected, the digital display shows: “――”
23
Indoor unit B room temperature (T
1
B)
24
Indoor unit C room temperature (T
1
C)
25
Indoor unit D room temperature (T
1
D)
26
Indoor unit E room temperature (T
1
E)
27
Indoor unit A evaporator temperature (T
2
A)
If the temperature is lower than -9
!
, the digital display shows “-9.” If the
temperature is higher than 70
!
, the digital display shows “70.” If the
indoor unit is not connected, the digital display shows: “――”
28
Indoor unit B evaporator temperature (T
2
B)
29
Indoor unit C evaporator temperature (T
2
C)
30
Indoor unit D evaporator temperature (T
2
D)
Service manual
MUEX-
H11 series
Содержание H11 Series
Страница 1: ...Service manual www mundoclima com CL21400 CL21407 MULTI INVERTER SERIE H11 R32...
Страница 11: ...10 MUEX 21 H11 3 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 12: ...11 MUEX 27 H11 3 Service manual MUEX H11 series...
Страница 13: ...12 MUEX 36 H11 4 Service manual MUEX H11 series...
Страница 14: ...13 MUEX 42 H11 5 Service manual MUEX H11 series...
Страница 41: ...EC 50 Open or short circuit of outdoor unit temperature sensor T3 T4 T5 Service manual MUEX H11 series 40...
Страница 73: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...