Temposonics
®
R-Series Powerlink V2
Operation Manual
I 25 I
Fig. 39: Replacement of the base unit (e.g. RH sensor), part 1
NOTICE
• If necessary, the sensor electronics of sensor model RD4 can be
replaced. Contact MTS Sensors for further information.
• Secure the base unit screws, e.g. using Loctite 243, before
re-installing.
Base unit
Sensor electronics housing
Plastic tube with inner
sensor element
Note:
The base unit will be delivered without
ground lug. Mount the ground lug at the
base unit. Ground the sensor via the
ground lug.
1. Loosen the screws
2 × socket head screw
M4×2.5
2. Pull out the base unit
4.7 Replacement of sensor
The base unit of the sensor models RH (RH-B) and RF (RF-C) is
replaceable as shown in Fig. 39 and Fig. 40. The sensor can be
replaced without interrupting the hydraulic circuit.
3. Insert the new base unit.
Mount the ground lug.
Tighten the screws.
Fastening torque
1.3 Nm
Fig. 40: Replacement of the base unit (e.g. RH sensor), part 2