Page 54 MSI-3750CS-5 RF Weighmeter • User Guide
3750CS
C
ELL
S
CALE RF DIGITAL WEIGHT INDICATOR
®
All Set Points Enable/Disable
1
OPER 2
2
GRTRTHAN
3
LT OR EQ
4
OPER 2
5
TRIGTYP2
6
GROSS
7
NETGROSS
8
TRIGTYP2
9
VALUE 2
10
NEW VAL2
11
3_
11
30_
11
300_
12
VALUE 1
13
OP RELAT
14
NONE
1) Push the UP or DOWN key until the “OPER 2” menu
appears
2) Push ENTER. The current Operator 2 function
appears.
3) Use the UP or DOWN key to scroll to the desired
operator.
In this example, we’ll use “LT or EQ” which means Less than or Equals.
4) Push ENTER.
5) Use the UP key to scroll to “TRIGTYP2”.
6) Push ENTER. The message shows the current trigger
type.
7) Use the UP key to choose the desired trigger type.
In this example we’ll program the “NETGROSS” mode
8) When the trigger type selection is displayed, push
ENTER.
9) Use the UP key to scroll to “VALUE 2”.
10) Push ENTER. The message reads “NEW VAL1”.
11) Use the numeric keys to enter a value for Value 1.
In this example we’ll program 300 lb..
12) When all digits are complete, push ENTER.
13) Use the UP or DOWN key to scroll to “OP RELAT”.
This is the menu which defines how the two thresh-
olds relate to each other.
14) Push ENTER. The message reads the current operator
relationship which defaults to “NONE”.
1
ALL SP
2
DISABLED
3
ENABLED
4
ALL SP
1) Push the UP or DOWN key until the “ALL SP” menu
appears
2) Push ENTER.
3) Use the UP or DOWN key to toggle between “DIS-
ABLED” and “ENABLED”.
4) Push ENTER.
This only enables SET POINTS that are turned ON. Individual Set Points
must be enabled also.
To add a second threshold for In-limits, out-of-limit, or grading applications.
This procedure is similar to the previous one except now we will program Value 2, Operator 2, Trigger Type 2, and add the Operator relationship. Since our example
Set Point is set to
≥
200 lb., by adding a
≤
300 lb. we’ll have an in-bounds comparator. Skip this procedure if only one threshold is needed.