7 Functions and settings
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
81
7.3.4
Setting desired value 2
Desired value 2 is activated if there is a continuous signal at GPI 5. The
GPI 5
must have previously been configured
(see "
Configurable inputs and
outputs
" on page 135) for this.
Setting range
Step size
Factory setting
49 V...140 V
0.1 V
100 V
Table 14
Setting range for desired value 2 in V
Setting range
Step size
Factory setting
0 kV... 9999 kV
0 kV...999.9 kV
0 kV...99.99 kV
1 kV
0.1 kV
0.01 kV
1kV
Table 15
Setting range for desired voltage value 2 in kV
To set desired value 2, proceed as follows:
1.
>
Control Parameters >
Vol-
tage Regulation > 1x
.
<01> Desired Value 2.
2. If you have already entered the
transformer
data
(page 111), press
to select the unit
you want: "V" or "kV".
3. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
4. Press
to increase the value or
to
reduce it.
5. Press
.
Desired value 2 is set.