7 Functions and settings
100
TAPCON® 230 basic
2117246/02 EN
© Maschinenfabrik Reinhausen 2012
7.3.12.9
Setting I< undercurrent limit value
As soon as the measured current falls below the set limit value, control is
blocked.
Setting range
Step size
Factory setting
0 % to 210 %
1 %
0 %
Table 25
Setting range for I< overcurrent limit value
To set the I< undercurrent limit value for undercurrent blocking, proceed as
follows:
1.
>
Control Parameters >
Limit
Values > 7x
.
<07> undercurrent I<.
2. Press
to increase the value or
to
reduce it.
3. Press
.
The I< undercurrent limit value is set.
7.3.12.10
Activating/deactivating I< undercurrent blocking
You can set the I< undercurrent limit value and then activate/deactivate un-
dercurrent blocking.
To activate the I< undercurrent blocking, proceed as follows:
1.
>
Control Parameters >
Limit
Values > 9x
<09> I> Undercurr. Blocking
2. Press
or
to to activate
(ON)/deactivate (OFF) undercurrent blocking.
3. Press
.
The I< undercurrent blocking is acti-
vated/deactivated.