![MR TAPCON 230 basic Скачать руководство пользователя страница 106](http://html.mh-extra.com/html/mr/tapcon-230-basic/tapcon-230-basic_operating-instructions-manual_1844354106.webp)
7 Functions and settings
106
TAPCON® 230 basic
2117246/02 EN
© Maschinenfabrik Reinhausen 2012
7.3.13.3
Setting the ohmic voltage drop Vr
The compensation effect can be rotated by 180° using the sign (-).
If you do not want to use a method of compensation, you must enter a "0".
Setting range
Step size
Factory setting
-25 V...25 V
0.1 V
0 V
Table 26
Setting range for ohmic voltage drop Vr line drop compensa-
tion
First you have to
select the "LDC" compensation method
(page 105).
To set the ohmic voltage drop Vr, proceed as follows:
1.
>
Control Parameters >
Com-
pensation > 1x
.
<01> Line Drop Compensation Vr.
2. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
3. Press
to increase the value or
to
reduce it.
4. Press
.
The ohmic voltage drop Vr is set.