7 Functions and settings
104
TAPCON® 230 basic
2117246/02 EN
© Maschinenfabrik Reinhausen 2012
If the active voltage drop "Vr" and reactive voltage drop "Vx" are set correctly,
then the voltage at the line end remains constant irrespective of the load.
Figure 30
Line drop compensation equivalent circuit
Figure 31
Line drop compensation
The settings for the compensation methods are described in more detail be-
low.