Setting range
Step size
Factory setting
0 A – 9999 A
1 A
0 A
Table 34
Setting range for primary transformer current
To set the primary transformer current, proceed as follows:
1.
>
Configuration >
Transformer
data > 2x
.
<02> Primary Current.
2. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
3. Press
to increase the value or
to
reduce it.
4. Press
.
The primary transformer current is set.
7.4.1.4
Setting the current transformer connection
To obtain a correct display, you must select a current transformer connection.
While "Unknown" is set for the current transformer connection, the current is
displayed as a percentage in relation to the selected measurement input. If
you select a current transformer connection, the absolute value (in amps) is
displayed.
The following values can be set:
1
A
5
A