7 Functions and settings
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
113
Setting range
Step size
Factory setting
0 kV... 9999 kV
0 kV...999.9 kV
0 kV...99.99 kV
1 kV
0.1 kV
0.01 kV
0 kV
Table 31
Setting range for primary transformer voltage
To set the primary transformer voltage, proceed as follows:
1.
>
Configuration >
Transformer
data.
<00> Primary Voltage.
2. Press
to highlight the decimal place.
The decimal place is defined and the value
can be changed.
3. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
4. Press
to increase the value or
to
reduce it.
5. Press
.
The primary transformer voltage is set.