7 Functions and settings
150
TAPCON® 230 basic
2117246/02 EN
© Maschinenfabrik Reinhausen 2012
7.6 Summary
of
setting
ranges
Parameter
name
Setting range
Step size
Factory setting
Desired value 1/2/3
49 V...140 V
0 kV... 9999 kV
0 kV...999.9 kV
0 kV...99.99 kV
0.1 V
1 kV
0.1 kV
0.01 kV
100 V
1 kV
1 kV
1 kV
Bandwidth
0.5 %...9%
0.01 %
2 %
Delay time T1
0 s...600 s
1 s
40 s
Delay time T2
1 s...10 s
0.1 s
10 s
V< Undervoltage (%)
60 %...100 %
of desired value
1 %
90 %
V< delay (signaling de-
lay time)
0 s...20 s
0.1 s
10 s
V> Overvoltage (%)
100 %...140 %
of desired value
1 %
110 %
I> Overcurrent
50 %...210 %
1 %
110 %
I< Undercurrent
0 %...210 %
1 %
0 %
Line drop compensa-
tion Vr
(ohmic voltage drop)
-25 V...25 V
0.1 V
0 V
Line drop compensa-
tion Vx
(inductive voltage drop)
-25 V...25 V
0.1 V
0 V
Z compensation
0 %...15 %
of desired value
0.1 %
0 %
Z compensation limit
value
0 %...15 %
of desired value
0.1 %
0 %
Primary transformer
voltage
0 kV... 9999 kV
0 kV...999.9 kV
0 kV...99.99 kV
1 kV
0.1 kV
0.01 kV
0 kV
0 kV
0 kV
Secondary transformer
voltage
57 V...123 V
0.1 V
100 V
Primary transformer
current
0 A – 9999 A
1 A
0 A
Raise/lower switching
pulse time
0 s...10 s
0.1 s
1.5 s
Regulator ID
0...9999
1
0
Operation counter
0...99999999
1
0
Function monitoring de-
lay time
0...120 minutes
1 minute
15 minutes