![MR TAPCON 230 basic Скачать руководство пользователя страница 107](http://html.mh-extra.com/html/mr/tapcon-230-basic/tapcon-230-basic_operating-instructions-manual_1844354107.webp)
7 Functions and settings
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
107
7.3.13.4
Setting the inductive voltage drop Vx
The compensation effect can be rotated by 180° using the sign (-).
If you do not want to use a method of compensation, you must enter a "0".
Setting range
Step size
Factory setting
-25 V...25 V
0.1 V
0 V
Table 27
Setting range for inductive voltage drop Vx line drop compen-
sation
First you have to
select the "LDC" compensation method
(page 105).
To set the inductive voltage drop Vx, proceed as follows:
1.
>
Control Parameters >
Com-
pensation > 2x
.
<02> Line Drop Compensation Vx.
2. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
3. Press
to increase the value or
to
reduce it.
4. Press
.
The inductive voltage drop Vx is set.