Section VIII
Trouble-Shooting Guide
006-0007207 MPC-1250DC Guide
Rev F
41 of 44
03/03/2022
LED
Indication
Possible Problem(s)
F0:
MPC Cooling
System LED
LED is BLINKING
GREEN
• Indicates that the fans are running at 67% of their rated speed. There
is no problem.
LED is AMBER
• Indicates that the fans are running at 100% of their rated speed.
There is no problem, but the unit is operating at a high ambient
temperature and a high load combination.
LED is RED
• Fans are running at 110% of rated speed to keep the unit cool. The
maximum recommended temperature may be exceeded, but the
fans are keeping things cool enough to avoid triggering the over‑
temperature shut‑down circuitry.
C0:
Fan Service
Required LED
LED is AMBER
• One or both fans have recently had degraded performance but
seem to be ok now. The MPC is running a diagnostic test.
LED is RED
• One or both fans presently have degraded performance, even
if they are running, and service is recommended at the earliest
convenient time.
• Ensure that the fan blades are not obstructed from turning
Audible
Alarm:
(pattern
repeats every
5 seconds)
Two tones
• The total MPC load power is above 1250 W.
• Loads should be reduced if this condition persists.
Three tones
• The DC OUTPUT has experienced either a short circuit or a load
having a start‑up surge current characteristic that the MPC could
not start. The DC OUTPUT is in hiccup mode.
• To reset the DC OUTPUT, turn the unit OFF. Clear the short circuit
fault on the end‑use equipment. Turn the unit back ON.