Section VI
Control Interface Details
006-0007207 MPC-1250DC Guide
Rev F
37 of 44
03/03/2022
Readback information that is available:
• AC Input Voltage
• AC Input Current
• AC Input Frequency
• DC Input Voltage
• DC Output Power
• External Switch Input Status
• Fan RPM
• Internal Temperatures
Parameters that are controllable through the interface:
• Output enable / disable
• Fan diagnostics
• Alarm enable / disable
For a detailed description of the terminal interface see the SynQor website at:
http://www.SynQor.com/UPS/documents/UPS_User_Commands.pdf
Ethernet Interface
The Ethernet interface provides a web page based user interface for monitoring and control
of the MPC. The user can configure email alerts for MPC alarm conditions. The interface also
exposes an SNMP interface compliant to RFC‑1628.
The Ethernet interface supports 10BASE‑T and 100BASE‑T standards. It utilizes a standard RJ‑45
connector, also allowing a metallic sealable circular military outer housing. The interface supports
auto‑negotiation, polarity correction, and Auto‑MDIX (detection and use of straight through or
cross‑over cables).
IP address assignment can be done via DHCP or user entry of a static address. The interface also
supports a direct connection between the MPC and a host computer by including a DHCP server
internal to the MPC.
For a detailed description of the Ethernet port and SNMP implementation see the SynQor website.
http://www.synqor.com/UPS/documents/UPS_Ethernet_SNMP_UG.pdf