6.2.4.
Keypad Commands and Control Input Definitions
F05
Range
Default
F05.046
Function assignment to key „UP“
0 … 17
0
0=
no function
1=
Substitute encoder frequency 1 by Set Value F03.030 (s)
2=
Substitute encoder frequency 2 by Set Value F04.042 (s)
3=
Substitute both encoder frequencies (1 and 2) (s)
4=
Freeze the actual frequency of encoder 1 *) (s)
5=
Freeze the actual frequency of encoder 2 *) (s)
6=
Freeze both encoder frequencies (1 and 2) *) (s)
7=
Release maintain / latch state of output 1 / relay 1 (d)
8=
Release maintain / latch state of output 2 / relay 2 (d)
9=
Release maintain / latch state of output 3 / relay 3 (d)
10= Release maintain / latch state of output 4 / relay 4 (d)
11= Release maintain / latch state of all outputs / relays (d)
12= Remote start-up delay, see F03.031 / F04.043 (s)
13= Cycle display (d)
14= Reset all min/max records to the actual display value (d)
15= n.a.
16= Read thumbwheel switches **) (d)
17= Start serial transmission (d)
F05.047
Function assignment to key „DOWN“
0 … 17
0
see key „UP“, F05.046
F05.048
Function assignment to key „ENTER“
0 … 17
0
see key „UP“,F05.046
*) The latest actual measuring value is temporary frozen. This will affect the display and the switching
outputs as well. The measuring procedure however will continue in the background.
**) Reading of the actual settings of the thumbwheels with models 642/644 (see chapter 8.3)
(s) = static function (on/off),
(d) = dynamic function, edge-triggered