CSD Series
Variable Frequency AC Drive
MOTORTRONICS
- 51 -
Fn98: XXX0:
Fault contact is
not
energized after overtorque (OL3) is detected.
XXX1:
Fault contact is energized after overtorque (OL3) is detected
XX0X:
Fault contact is
not
energized after electronic thermal motor
protection (OL1) is acting.
XX1X:
Fault contact is energized after electronic thermal motor
protection (OL1) is acting.
X0XX:
Fault contact is normal open (N.O.).
X1XX:
Fault contact is normal closed (N.C.).
0XXX:
Fault contact is
not
energized after electronic thermal drive
protection (OL2) is acting
1XXX:
Fault contact is energized after electronic thermal drive
protection (OL2) is acting
Fn99: Reserved
Communication Mode
Fn100 - Fn102 define the communication parameters of the drive.
Fn100 = Communication identification number - Factory Setting = 1;
Range = 1 - 32
Fn100 provides an identification number to each individual drive for
communications. When using more than one drive in a
communications loop, ensure that each individual drive has a unique
identification number programmed into Fn100. Having more than one
drive in a communications loop with the same ID number will cause
communications conflicts.
Fn101 = Baud rate of communication - Factory Setting = 1;
Range = 0/1/2 (4800/9600/19200)
Fn101 defines the baud rate of communication between drives and the
host computer. Ensure that all devices in a communication loop are
programmed to the same baud rate.
Fn102 = Communication agreement - Factory Setting = 1100; Range =
XXX0:
1 stop bit
XXX1:
2 stop bits
XX0X:
Even parity
XX1X:
Odd parity
X0XX:
Without parity
X1XX:
With parity
0XXX:
8 bits data
1XXX:
7 bits data
Fn102 defines for the drive the characteristic of the communication
string. There are basically two styles of communication that can be
performed with the drive. Using the RS485 Kit, up to 32 drives can be
connected to one host computer for control. Using the RS232 Kit, one
drive can be connected to a host computer for both control and
programming functions. Software exists for both modes using a
standard PC as the host computer. If the application requires custom
programming, copies of the drive protocol can be obtained from
Motortronics
Fn103 - Fn122 = Reserved
Содержание CSD Series
Страница 2: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 74 ...
Страница 4: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 76 ...
Страница 30: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 26 ...
Страница 32: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 28 ...
Страница 65: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 61 ...
Страница 74: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 70 Prepared By Date Set By Date Received By Date ...