CSD Series
Variable Frequency AC Drive
MOTORTRONICS
- 13 -
Diode Ratings
AC Coils DC Coils
*
*Current >
Voltage > 2 X Coil
Coil VA
Coil Voltage
DC Snubber
Figure 3 - 4
Typical Components
AC Snubber Ratings
Table 3 C
3.6 Line Reactors
•
Source KVA must be limited to less than 500 KVA to protect against
premature rectifier assembly failure. If source KVA exceeds 500 KVA,
installation of appropriate reactor is required. If multiple drives are used,
installation of individual reactors is not required (one reactor capable
of combined amperage is acceptable).
Table 3 D - Suggested Line Reactor Values
Model Number
Part Number
Current (Amps)
Inductance
(mH)
CSD-2P5, 201
10-RL-00402
4
6
CSD -202
10-RL-00802
8
3
CSD-203
10-RL-01202
12
2.5
CSD-205
10-RL-01802
18
1.5
CSD-207
10-RL-02502
25
1.2
CSD-210
10-RL-03502
35
0.8
CSD-215
10-RL-04502
45
0.7
CSD-220
10-RL-05502
55
0.5
CSD-230
10-RL-08002
80
0.4
CSD-401
10-RL-00202
2
20
CSD-402, 403
10-RL-00403
4
9
CSD-405
10-RL-00803
8
5
CSD-407
10-RL-01203
12
4.2
CSD-410
10-RL-01803
18
2.5
CSD-415
10-RL-02503
25
2.0
CSD-420
10-RL-03503
35
1.2
CSD-430
10-RL-04503
45
1.2
Содержание CSD Series
Страница 2: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 74 ...
Страница 4: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 76 ...
Страница 30: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 26 ...
Страница 32: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 28 ...
Страница 65: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 61 ...
Страница 74: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 70 Prepared By Date Set By Date Received By Date ...