CSD Series
Variable Frequency AC Drive
MOTORTRONICS
- 44 -
16-31: Changes 00-15 N.O. (normally open) contact to N.C. (normally
closed) contact
Fn59 - Fn 60 = Reserved
Fn61 = Digital Multifunction Output - Factory Setting = 00;
Range = 00 - 11
The open collector transistor output of TM1 pins 10 & 11 are used for
several indications. Note that TM2 pins 10 and 11 is an open collector
output rated for 50mA, 35 VDC. Do not apply AC voltage to this contact.
Applying AC voltage to this contact will cause failure of the drive. Also
applying DC voltage in the reverse polarity will cause failure of the
drive. Program Fn61 for the style of control required of the open collector
output. Entering a value 00-05 equals normally open (N.O.) contacts
and entering a value of 06-11 equals normally closed (N.C.) contacts.
Following is a description of functions for certain values of Fn61:
00/06: Run mode
places the open collector output transistor in the run mode.
Whenever, the output of the drive is > 0 Hz, the transistor will be on.
When the output of the drive is = 0 Hz, the transistor will be off.
Programing Fn61 = 06 places the open collector output transistor in
the run mode. Whenever the output of the drive is > 0 Hz, the transistor
will be off. When the output of the drive is = 0 Hz the transistor will be
on.
01/07:
Up to desired frequency
Fn61 = 01 places the open collector output
transistor in the up to desired frequency mode. Whenever the output
of the drive is at constant speed, the transistor will be on. When the
drive is not up to desired frequency the transistor will be off.
Programming Fn61 = 07 places the open collector out put transistor
in the up to desired frequency mode. Whenever the output of the drive
is at constant speed the transistor will be off. When the drive is not up
to the desired frequency the transistor will be on.
02/08: Set frequency output - Fn08+/- Fn09
places the open collector output
transistor in the bandwidth mode. Whenever the output of the drive is
in agreement with the value in Fn08 plus or minus the value in Fn09
the transistor will be on. When the output of the drive is not in agreement
with the value in Fn08 plus or minus the value in Fn09, the transistor
will be off. Programming Fn61 = 08 places the open collector output
transistor in the band width mode. Whenever the output of the drive is
in agreement with the value in Fn08 + Fn09 the transistor will be off.
When the output of the drive is not in agreement with the value in Fn08
+ Fn09, the transistor will be on.
03/09:
Frequency detection > Fn08
Places the open collector output transistor in the frequency detection
greater than mode. Whenever the output of the drive is > Fn08 the
transistor will be on. Whenever the output of the drive is < Fn08 the
transistor will be off. Programming Fn61 = 09 places the open collector
output transistor in the frequency detection greater than mode.
Whenever the output of the drive is > Fn08 the transistor will be off.
Содержание CSD Series
Страница 2: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 74 ...
Страница 4: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 76 ...
Страница 30: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 26 ...
Страница 32: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 28 ...
Страница 65: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 61 ...
Страница 74: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 70 Prepared By Date Set By Date Received By Date ...