CSD Series
Variable Frequency AC Drive
MOTORTRONICS
- 33 -
*For 0-5 VDC analog command signal control:
connect the command
signal positive to TM2-13 and the command signal negative toTM2-14.
Also install the shorting plug on JP1 pins 1 and 2.
*For 0-10 VDC analog command signal control:
connect the command
signal positive to TM2-13 and the command signal negative to TM2-
14. Also install the shorting plug on JP2 pins 2 and 3.
*For 4-20MA analog command signal control:
connect the command
signal positive to TM2-13 and the command signal negative to TM2-
14. Also install the shorting plug on JP1 pins 2 and 3.
*For potentiometer control:
connect the fully clockwise position of
the potentiometer to TM2-12, connect the wiper of the potentiometer
to TM2-13 and connect the fully counter clockwise position of the
potentiometer to TM2-14.
Note: The start/stop command is set via the potentiometer on the
keypad when Fn11 = 1 and any multi function terminal (Fn56-58) is
programmed as an open control signal selector switch (Fn56-58 =
9). The start/stop command is keypad controlled when the signal
selector switch is closed and Fn56-58 = 9.
Note: The start/stop command is set via the analog input on TM2
pins 12 - 14 when Fn11 = 2 and any multifunction terminal (Fn56-58)
is programmed as an open control signal selector switch (Fn56-58 =
9). The start/stop command is keypad controlled when the signal
selector switch is closed and Fn56-58 = 9.
3: (Up/Down)
Run by multi-function input frequency command
(terminals 6-8)
When Fn11 = 3 and if Fn56-58 = 12 or 13, the multifunction input
terminals TM2 pins 6 - 8 act as arrow keys to increase and decrease
speed. Programming Fn56 - 58 = 12 changes that particular terminal
to an up command. Programming Fn56 - 58 = 13 changes that
particular terminal to a down command. When the run command is
on, the drive will accelerate to the frequency in Fn25. When the up
command is on, the drive starts to accelerate. When the up command
is off, the drive will stop accelerating and run at constant speed. When
the down command is on the drive will start to decelerate and when
the down command is off the drive will run at constant speed.
Fn12 = Stall Prevention During Accel/Decel/Running:
XXX0:
Stall prevention during accel enabled
This setting allows the drive to automatically extend the acceleration
time if it detects a stall condition beginning to occur.
XXX1:
Disables stall prevention during accel (the above feature)
XX0X:
Stall prevention during decel enabled
This setting allows the drive to automatically extend the deceleration
time if it detects a stall condition beginning to occur.
XX1X:
Disables stall prevention during decel disable (the above feature)
X0XX:
Stall prevention during running enabled
This setting allows the drive to automatically lower frequency to closely
match the motor speed and when the stall condition has cleared, will
reaccelerate the motor back to operational speed.
X1XX:
Disables stall prevention during running (the above feature)
0XXX:
Stall prevention decel time set by Fn02
The rate at which the drive output will decelerate is dependent upon
the programming of the left most digit of Fn12. If Fn12 = 0XXX
deceleration rate = Fn02.
1XXX:
Stall prevention decel time set by Fn15.
If Fn12 is 1XXX the deceleration rate = Fn15.
Содержание CSD Series
Страница 2: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 74 ...
Страница 4: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 76 ...
Страница 30: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 26 ...
Страница 32: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 28 ...
Страница 65: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 61 ...
Страница 74: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 70 Prepared By Date Set By Date Received By Date ...