CSD Series
Variable Frequency AC Drive
MOTORTRONICS
- 45 -
Whenever the output of the drive is < Fn08 the transistor will be on.
04/10: Frequency detection < Fn08
Places the open collector output transistor in the frequency detection
less than mode. When the output of the drive is < Fn08 the transistor
will be on. Whenever the output of the drive is > in Fn08 the transistor
will be off. Programming Fn61 = 10 places the open collector output
transistor in the frequency detection less than mode. When the output
of the drive is < Fn08 the transistor will be off. Whenever the output of
the drive is > Fn08 the transistor will be on.
05/11:
Over torque detection
places the open collector output transistor in
the overtorque detection mode. Whenever the drive detects an
overtorque condition in the load, the transistor will turn on. When the
drive does not detect an overtorque condition in the load, the transistor
will turn off. Programming Fn61 = 11 places the open collector output
transistor in the overtorque detection mode. Whenever the drive detects
an overtorque condition in the load, the transistor will turn off. When
the drive does not detect an overtorque condition in the load, the
transistor will turn on.
Note: Regardless of programming, when power is removed from the
drive the transistor will be off.
06-11:
Changes Fn61 from normally off (open) to normally on (closed) control.
Fn62 - Fn 64: Reserved
Fn65 - Fn68: Prohibited Frequency Control
Fn65 = Setting prohibited freq. 1 - Factory Setting = 0 Hz;
Range = 0 - 400 Hz
Fn66 = Setting prohibited freq. 2 - Factory Setting = 0 Hz.;
Range = 0 - 400 Hz
Fn67 = Setting prohibited freq. 3 - Factory Setting = 0 Hz.;
Range = 0 - 400 Hz
Fn68 = Setting prohibited freq. range (bandwidth) -
Factory Setting = 0 Hz.; Range = 0 - 400 Hz
Fn65 - Fn68 can be used to program up to three prohibit frequency
control ranges. These can be used to prevent mechanical oscillation
that may occur at certain frequencies. Fn65 - Fn67 determine the
three distinct frequency setpoints to be avoided by the drive. Fn68
defines the band width around these frequencies to be avoided by
the drive. For example:
When Fn65 = 10.0 Hz, Fn66 = 20.0 Hz, Fn 67 = 30.0 Hz, Fn68 = 2.0 Hz
The skip freq. ranges are:
10 Hz + 2 Hz = 8 - 12 Hz
20 Hz + 2 Hz = 18 - 22 Hz
30 Hz + 2 Hz = 28 - 32 Hz
Electronic Thermal Protection (motor and drive)
Fn69 - Fn71 define the thermal protection schemes to be used to
protect the drive and the motor.
Содержание CSD Series
Страница 2: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 74 ...
Страница 4: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 76 ...
Страница 30: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 26 ...
Страница 32: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 28 ...
Страница 65: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 61 ...
Страница 74: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 70 Prepared By Date Set By Date Received By Date ...