Troubleshooting
29
Manual # 42-02-U001, Rev C1
Troubleshooting
Topics addressed:
• Normal Operation Review
• Utility power normal but UPS on battery mode
• Fault LED lighted; no output
• UPS fails to work when power fails
• No LEDs and no output
• Board troubleshooting
• UPS troubleshooting
TAPS Operation Review
Commercial Power Present
• TAPS backup power source charges automatically
• TDJ relay picks, enabling
KMO
contactor to pick and opening the feed to the P1 input on
the TAPS-VF board
•
KMO
contactor picks, shunting power directly to the controller and disabling the
KM5
contactor (
KMO
interlocked with
KM5
)
• Indicator NORMAL POWER lights green
Commercial Power Lost
• TDJ relay drops, disabling
KMO
contactor and closing feed to the P1 input on the TAPS-VF
board
• UPS supplies single phase AC output to power transformer T1,
KM5
contactor picks, pro-
viding backup power to control
• Indicator BACKUP POWER lights amber
Note
Elevator safety string remains functional when backup power is provided so that no electrical
protective devices are rendered ineffective.
Main Line Disconnect Open
This disconnect is a contact between terminals BS1 and BS2.
Please refer to “Control Wires BS1
• 24V+ signal to TAPS-VF board removed via an auxiliary contact on the disconnect switch
(pole 4), ensuring that the
KMO
and
KM5
contactors will not pick.
Содержание TAPS
Страница 6: ...2 Manual 42 02 D001 Rev A 1 September 2003...
Страница 15: ...Installation 9 Manual 42 02 U001 Rev C1 Figure 5 6kVA UPS Enclosure Base Assembly...
Страница 16: ...10 Manual 42 02 U001 Rev C1 Figure 6 6kVA UPS Enclosure Assembly...
Страница 40: ...34 Manual 42 02 U001 Rev C1 6kVA Units The 6kVA unit uses an LCD as well as LEDs...
Страница 42: ...36 Manual 42 02 U001 Rev C1 6 12 12...
Страница 43: ...TAPS Drawings 37 Manual 42 02 U001 Rev C1...
Страница 44: ...38 Manual 42 02 U001 Rev C1...
Страница 45: ...TAPS Drawings 39 Manual 42 02 U001 Rev C1...