Startup
21
Manual # 42-02-U001, Rev C1
Startup
1. Ensure that the AC/TAPS DISCONNECT switch is in the OFF position.
2. Check that all the connections (TAPS and UPS) have been properly made.
3. Position all necessary switches so that the elevator is in inspection mode during power
up.
4. Make sure that the TAPS BYPASS switch is in the BYPASS position.
5. Turn on the main line disconnect.
6. Turn the AC/TAPS DISCONNECT switch to the ON position.
7. Set the utility breaker switch on the back of the UPS to the “ON” position.
8. Turn the UPS on.
• For 3 kVA units, simply press the power button on the front. After a few seconds the
UPS will begin the boot up sequence. Once boot up is complete, make sure the 100%
utility and 75% inverter LEDs are on. (Both LEDs are on the front of the 3kVA UPS.)
Note: If either the Fault, 50% Battery Low, or 25% Overload LEDs are on, see Trouble-
shooting on
.
• For 6kVA units, press and hold the ON button for at least 3 seconds. After a few sec-
onds the UPS will begin a self TEST, followed by an OK message, and then display:
Verify the UPS Utility and Bypass voltage LEDs are lighted. (If the Error LED lights,
see Troubleshooting on
9. Verify the TAPS NORMAL POWER indicator (green) is on (next to the AC/TAPS discon-
nect switch).
10. Verify contactor
KM0
picks after a few seconds. When this contactor picks, there should
be power to the controller.
11. Check for any AC phasing problems at the elevator controller and that the elevator com-
puter, motor drive, and brake units have power.
12. ONLY if you have a 6kVA TAPS unit and the line voltage feeding your elevator con-
troller is 208 or 240VAC, you must set the UPS output to match.
For all other units, skip
to Set Parameters on
When the UPS has completing “booting”, the
overbar displayed above LINE-UPS-LOAD will
disappear.
UPS Utility Voltage
UPS Bypass Voltage
ERROR
Содержание TAPS
Страница 6: ...2 Manual 42 02 D001 Rev A 1 September 2003...
Страница 15: ...Installation 9 Manual 42 02 U001 Rev C1 Figure 5 6kVA UPS Enclosure Base Assembly...
Страница 16: ...10 Manual 42 02 U001 Rev C1 Figure 6 6kVA UPS Enclosure Assembly...
Страница 40: ...34 Manual 42 02 U001 Rev C1 6kVA Units The 6kVA unit uses an LCD as well as LEDs...
Страница 42: ...36 Manual 42 02 U001 Rev C1 6 12 12...
Страница 43: ...TAPS Drawings 37 Manual 42 02 U001 Rev C1...
Страница 44: ...38 Manual 42 02 U001 Rev C1...
Страница 45: ...TAPS Drawings 39 Manual 42 02 U001 Rev C1...