TAPS to Controller Signal Connections
Figure 8. Relay Control Wiring Between TAPS and Elevator Controller
Output Signals
Note
Output Ratings: All outputs use single-pole relays with Normally Open (N.O.) contacts, each
with its own common (dry contact) which can be used on non-ground referenced signals and
have the following ratings: 3A maximum inductive load rating, 5A maximum resistive load rat-
ing, 125 VAC or 30 VDC maximum voltage.
• BACKUP POWER ON #1 OUTPUT: Terminals UPS1, CM3. This output contact will
activate (close) when TAPS is in backup power mode. When this output activates, the con-
trol system must move the elevator to the next landing at approximately 10 fpm, and pref-
erably with very low acceleration, deceleration, and jerk rates.
• BACKUP POWER ON#2 OUTPUT: Terminals UPS2, CM4. This output is identical to
the BACKUP POWER ON #1 OUTPUT. This output is used with controllers that use the
drive internal speed patterns. This contact should be wired to the drive to select a more
relaxed profile, mainly with lower acceleration, deceleration, and jerk rates.
Note
The TAPS unit will attempt to provide the full current load demanded by the machine. In doing
so, voltage may be reduced. If voltage falls below the undervoltage protection level set in your
AC drive, an undervoltage condition will be reported. You may need to set the drive parameter
for undervoltage detection to a lower value to prevent this.
• REVERSE DIRECTION OUTPUT: Terminals REV, CM6. This output contact will acti-
vate (close) when TAPS determines that the initial direction of travel is not the optimal
direction because it will require excessive power. When the controller receives this signal,
it must stop the elevator, then move in the opposite direction.
• RUN UP OUTPUT: Terminals UP, CM7. This output contact will activate (close) when
TAPS determines that the controller must move in the up direction.
RUNDOWN
RUN UP
BACKUP POWER #1
BACKUP POWER #2
REV DIRECTION OUT
FAULT MONITOR OUT
Содержание TAPS
Страница 6: ...2 Manual 42 02 D001 Rev A 1 September 2003...
Страница 15: ...Installation 9 Manual 42 02 U001 Rev C1 Figure 5 6kVA UPS Enclosure Base Assembly...
Страница 16: ...10 Manual 42 02 U001 Rev C1 Figure 6 6kVA UPS Enclosure Assembly...
Страница 40: ...34 Manual 42 02 U001 Rev C1 6kVA Units The 6kVA unit uses an LCD as well as LEDs...
Страница 42: ...36 Manual 42 02 U001 Rev C1 6 12 12...
Страница 43: ...TAPS Drawings 37 Manual 42 02 U001 Rev C1...
Страница 44: ...38 Manual 42 02 U001 Rev C1...
Страница 45: ...TAPS Drawings 39 Manual 42 02 U001 Rev C1...