24
Manual # 42-02-U001, Rev C1
* If F1-A is incorrectly set, TAPS functions including UPS reset and backup power output volt-
age check will not function properly.
Table 7. Menu Parameter Values
Param
#
Parameter
Name
Description
Units
Range
MCE
User
Setting
FUN1-TAPS Adjustment Settings
F1-1
Backup
Power run-
time
Set number of minutes TAPS will run during
back up operation. This can be determined by
testing as below:
1. Move car to center of tallest floor.
2. Perform a back-up operation.
3. Increase the time taken by one minute and
enter that time here.
Minutes 0000 -
0099
8
F1-2
Backup
power level
TAPS will first attempt to move car to nearest
landing. If current drawn by that operation
exceeds percentage set here, TAPS will pause
car to reverse direction. Typically set to 65%. *
See note following table.
%
0000 -
0099
65
F1-3
Time from
REV to DWN
output
REV output is used to pause car if current set-
ting is exceeded. The DWN output will then start
car moving in down direction. This setting deter-
mines how long the car should be “paused”
before it begins moving down.
Seconds 0000 -
0099
3
F1-4
Time from
UP to REV
output
UP output starts initial, up movement of car. If
current setting is exceeded, REV output will
pause car. This setting determines how long
TAPS should allow current setting to be
exceeded before REV output is activated.
Seconds 0000 -
0099
3
F1-5
Backup
Power Start
voltage
Minimum battery cell voltage required to start
backup operation. If cell voltage falls below this
setting, the TAPS unit will not attempt to start.
Must be less than F2-06 battery voltage display.
Volts
0000–
13.00
12.50
F1-6
Backup
Power volt-
age
During backup, the minimum battery cell volt-
age needed to continue backup operation. Must
be less than F1-05 value. Error E-04 will be dis-
played.
Volts
0000 –
F1-5
10.80
F1-7
Backup
Power Out-
put Voltage
Low Limit
If backup voltage drops below this level, the
TAPS unit will shutdown. Error E-05 or E-07 will
be displayed.
Volts
0000 -
0219
90 for 1
and
3kVA,
165 for
6kVA
F1-8
Output Test
FACTORY TEST ONLY!
Must be set to 0 at all times.
F1-9
Commercial
Power Loss
Detection
Time
Determines duration of power outage before
TAPS will begin backup power operation.
Seconds 0000 -
0099
2
F1-A*
UPS model
selection
0 = 1 or 3kVA unit
1 = 6kVA unit
0 or 1
F1-B
Rescue Com-
plete (P3)
execution
delay timer
Sets a delay in responding to the Rescue Com-
plete (P3) signal. The Rescue Complete input
will be executed as soon as the timer expires or
immediately if the timer has already expired.
Seconds 0 -60
0
Содержание TAPS
Страница 6: ...2 Manual 42 02 D001 Rev A 1 September 2003...
Страница 15: ...Installation 9 Manual 42 02 U001 Rev C1 Figure 5 6kVA UPS Enclosure Base Assembly...
Страница 16: ...10 Manual 42 02 U001 Rev C1 Figure 6 6kVA UPS Enclosure Assembly...
Страница 40: ...34 Manual 42 02 U001 Rev C1 6kVA Units The 6kVA unit uses an LCD as well as LEDs...
Страница 42: ...36 Manual 42 02 U001 Rev C1 6 12 12...
Страница 43: ...TAPS Drawings 37 Manual 42 02 U001 Rev C1...
Страница 44: ...38 Manual 42 02 U001 Rev C1...
Страница 45: ...TAPS Drawings 39 Manual 42 02 U001 Rev C1...