Installation
7
Manual # 42-02-U001, Rev C1
Figure 4. 6 kVA UPS Chassis and Mounting Dimensions
Electrically, the TAPS unit is installed between the main disconnect and the elevator controller.
Choose the location that will allow the shortest power and signal wires. Depending on the site,
there are approximately 5 to 20 control signal wires and 8 power wires. In general, when an iso-
lation transformer is part of the control system, the TAPS unit is placed electrically between the
transformer and the controller. When TAPS is used with an MCE controller, please refer to the
specific job prints.
Power wires must be routed in separate conduit from signal wires to prevent the power wires
from radiating noise into the signal wires. All applicable local, state, and other building codes
must be followed.
Caution
Provide at least 1.0” ventilation space between cabinets and any wall or obstruction.
18 in
32 3/8 in
21 3/8 in
32 3/8 in
6 13/16 in
34 in