Control Wires BS1 and BS2
1. A means is required to prevent the TAPS unit from delivering power to the elevator con-
troller when AC power is deliberately shut off at the main disconnect. This is accom-
plished by disabling 24 VDC power to the TAPS-VF board by placing a switch or contact
across terminals BS1 and BS2 on the front of the TAPS connector plate as shown below:
2. Wire the auxiliary contact of the main disconnect between BS1 and BS2 so that, when
the main disconnect is opened, the connection between the two is likewise opened.
Transformer Configuration: 3 kVA Units ONLY
If you have a 6 kVA unit, skip this section. ONLY 3 kVA units require transformer configuration.
Please refer to “Transformer Jumper Schedule, 3 kVA TAPS Units” on page 13
Figure 7. 3 kVA TAPS Transformers
Auxiliary contact on the
disconnecting means
that is positively opened
mechanically and whose
opening is not solely
dependent on springs.
If shunt trip breaker is
used, wire a contact in
series with disconnect
contact that will open if
shunt trip breaker acti-
vates.
T1, output transformer
T2, input transformer
Содержание TAPS
Страница 6: ...2 Manual 42 02 D001 Rev A 1 September 2003...
Страница 15: ...Installation 9 Manual 42 02 U001 Rev C1 Figure 5 6kVA UPS Enclosure Base Assembly...
Страница 16: ...10 Manual 42 02 U001 Rev C1 Figure 6 6kVA UPS Enclosure Assembly...
Страница 40: ...34 Manual 42 02 U001 Rev C1 6kVA Units The 6kVA unit uses an LCD as well as LEDs...
Страница 42: ...36 Manual 42 02 U001 Rev C1 6 12 12...
Страница 43: ...TAPS Drawings 37 Manual 42 02 U001 Rev C1...
Страница 44: ...38 Manual 42 02 U001 Rev C1...
Страница 45: ...TAPS Drawings 39 Manual 42 02 U001 Rev C1...