![Morningstar TriStar MPPT 600V Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/morningstar/tristar-mppt-600v/tristar-mppt-600v_installation-and-operation-manual_1834372034.webp)
34
Installation
Step 9 - Adjust Settings Switches
Switch 1: Future Use
Select the charging source that will be connected to the TS-MPPT-600V-TR.
Mode
Switch 1
Solar Charging
OFF
Future Use
ON
Switch 2: Not Used (OFF)
Switch 3: Charging Mode
Charging Mode
Switch 3
Normal 48V
OFF
Custom Multiplier*
ON
*
Allows for nominal charging voltages of 24, 36, or 60V. Battery compatibility must be verified.
Switches 4, 5, & 6: Battery Charging Settings
It is important to select the battery type that matches the system battery to ensure proper charg-
ing and long battery life. Refer to the specifications provided by the battery manufacturer and
choose a setting that best fits the recommended charging profile.
Settings
Switches
4 - 5 - 6
Battery
Type
Absorp.
Stage
(Volts)
Float
Stage
(Volts)
Equalize
Stage
(Volts)
Equalize
Interval
(Days)
off-off-off
1 - Gel
56.00
54.80
off-off-on
2 - Sealed*
56.60
54.80
57.60
28
off-on-off
3 - Sealed*
57.20
54.80
58.40
28
off-on-on 4 - AGM/Flooded
57.60
54.80
60.40
28
on-off-off
5 - Flooded
58.40
54.00
61.20
28
on-off-on
6 - Flooded
58.80
54.00
61.60
28
on-on-off
7 - L-16
61.60
53.60
64.00
14
on-on-on
8 - Custom
Custom
Custom
Custom
Custom
* “Sealed” battery type includes gel and AGM batteries
All settings are for 48 volt nominal systems. Descriptions of battery type and stages are provided
below. See section 4.2 for full details.
Battery Type
- The most common battery type associated with the specified charging settings.
Absorption Stage - This stage limits input current so that the Absorption voltage is maintained.
As the battery becomes more charged, the charging current continues to taper down until the
battery is fully charged.