The Interface Solution Experts 

7

FDY

PC-Programmable Frequency

Transmitter and Display

PC Confi guration Software

The FDY PC Confi guration Software is used to 
program all of the FDY’s parameters.  For detailed 
information on how to use our confi guration software, 
access our HelpMap Navigation System.  The PC 
Software is made up of these sections:

1.  

Program Status & Device ID

–The 

Program 

Status

 portion of the screen displays the activity of 

the connected unit.  It will show you if the unit is 

Idle

Uploading

Downloading

 or 

Monitoring

.  

Device ID

 

displays the type of device that is being polled and its 
ID number.

2.  

Tag/Descriptor/Message

–These boxes are used 

to program a FDY with an individual tag, descriptor or 
message used for easily identifying the unit.  The 

Programmed Date

 stores the last time that the unit’s 

confi guration was updated.

3.  

Device Confi guration

–Displays the current 

confi guration of the attached FDY. 

4.  

Measurement Mode

–The drop-down menu selects 

which type of measurement the FDY will monitor.
5. 

 Variables/Device Status/Communications

These sections display the status of the FDY and its 
process.  The 

Variables

 section displays the input 

to the FDY, FDY output and the percent of span.  
The 

Device Status

 provides advanced diagnostic 

information on the FDY.  The 

Communications

 box 

displays the status of the FDY’s communication with 
the PC Program.

6.  

Input/Range/Output/Trimming/Custom Curve 

Tabs

–These tabs change the right side of the screen 

to allow you to set the appropriate part of the FDY’s 
confi guration.  See corresponding sections of this 
manual for additional information on these tabs.

7.  

Quickset Buttons  

                 –These buttons 

allow you to program just one part of the FDY’s 
confi guration program.  From left to right, they 
program: 

Fail Mode

,

 Display Mode

,

 Tag

 and 

Message

Figure 4.

  D-BOX Enclosure Dimensions

4mm

3.3  in

11 mm

4.65 in

13 mm

5.12 in

INST M NT

T

116mm

4.56 in

27mm

1. 5 in

C ND IT

FITTIN

C

DY

1mm

3.2  in

FDY

C M

PS

–PS

6027.8

H Z

Содержание FDY

Страница 1: ...FDY FDYNovember 2013 165 730 00E1 PC Programmable Frequency Transmitter and Display PC Programmable Frequency Transmitter and Display...

Страница 2: ...ters 9 Programming the Input Parameters 9 Programming the Range Parameters 10 Programming the Output Parameters 11 Programming the Trimming Parameters 12 Sensor Trimming 12 Output Trimming 13 Loop Tes...

Страница 3: ...eatures a large integral display that shows real time process status About this Manual Wherever you see a Note Caution or WARNING pay particular attention A Note provides information to help you in av...

Страница 4: ...kohms typical 1kHz for input 6V for 0 02 30AC model 125kohms for 10 250AC model Load Capability 508 ohms 24V Output Current Limiting 3 8mA and 21 4mA for input under range and over range 3 6mA and 23...

Страница 5: ...Hz Table 6 Period Input Parameters Resolution 1mV 1mV 1mV Range 0 01 1 5V 0 002 0 15V 0 002 0 15V Hysteresis Measured Period 40 sec to 50sec 40 sec to 2sec 40 sec to 2sec Input Range 100mV 30V DC Reso...

Страница 6: ...3 25 in 62mm 2 45 in 64mm 2 50 in 66mm 2 58 in 76mm 3 00 in 43mm 1 70 in 18mm 0 70 in FDY COM PS 0 PS 0 6027 8 HZ Figure 2 FDY Dimensions 65mm 2 55 in GND GND 1 2 NPT 1 2 NPT 102mm 4 00 in 129mm 5 06...

Страница 7: ...rrent configuration of the attached FDY 4 Measurement Mode The drop down menu selects which type of measurement the FDY will monitor 5 Variables Device Status Communications These sections display the...

Страница 8: ...ion Program 1 2 3 4 5 6 7 Default Factory Configurations The following are the default factory settings for your unit Input Measurement Mode Frequency 0 100Hz Input Hysteresis 10mV Timeout Period 10s...

Страница 9: ...ions Cable Communications Software Programming the FDY All operating parameters of the FDY are set using a PC a serial communication cable and Moore Industries Intelligent PC Configuration software Wh...

Страница 10: ...ed to set this to the default setting of 2V maximum is 2 5V For input voltages below 3V it is recommended to set this to 2 3 of the peak to peak p p input signal voltage plus the low state signal volt...

Страница 11: ...ed reading This can be used to compensate for bent blades in a monitored turbine by setting the value to equal the number of blades on the turbine i e if the turbine has four blades set the Averaging...

Страница 12: ...ox This reduces the effect of sudden spikes and helps stop unnecessary alarms by smoothing the reading Failure Mode Failure Mode lets you set the output of the transmitter when it is malfunctioning It...

Страница 13: ...attempt to trim the FDY ensure that the correct sensor is attached to the transmitter then go to the Trimming tab as shown at the left and 1 Select the User radio button under Trim Mode then answer Y...

Страница 14: ...e output will no longer be fixed at 4mA 4 Continue by clicking the Fix Current High button This should cause the FDY to output 20mA If the output is a different value enter it into the Output Current...

Страница 15: ...int of the transmitter and the transmitter will send out a 4mA signal or the selected output signal if the zero output is set at a value other than 4mA when this point is reached Likewise the point yo...

Страница 16: ...onfiguration program you are ready to download the configuration file Downloading the Configuration File After the configuration has been set to your satisfaction it can be downloaded to the unit by s...

Страница 17: ...signal wiring should be 2 inches Note Some of Moore Industries instruments can be classified as receivers IPT2 IPX2 etc and some can be classified as transmitters TRX TRY etc while some are both a rec...

Страница 18: ...eas requiring intrinsically safe instrumentation Refer to the Special Conditions outlined below before proceeding with installation Special Conditions of Use The following instructions must be adhered...

Страница 19: ...The Interface Solution Experts 19 FDY PC Programmable Frequency Transmitter and Display...

Страница 20: ...isions of the Directive Fulfilled by the Equipment Group II Category 1G EEx ia IIC T4 Notified Body for EC Type Examination LCIE Notified Body Number 0081 33 av du G n ral Leclerc 92260 Fontenay aux R...

Страница 21: ...EC Type Examination Certificate ISSeP 08 ATEX 033 X Technical Standards Used EN 60079 0 2006 Explosive atmospheres Part 0 Equipment General requirements EN 60079 1 2007 Explosive atmospheres Part 1 Eq...

Страница 22: ...IES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVE...

Отзывы: