PC-Programmable Frequency
Transmitter and Display

Output Trimming

Output Trimming increases the accuracy of your 
transmitter by matching the reading of its recorded 
output to its actual output. Essentially, this means that 
it will eliminate any error in the unit that is reading the 
FDY’s output. 

To start trimming the output, hook-up the transmitter 
in the loop shown in Figure 6, and connect either a 
multimeter (preferably), or the unit that will be reading 
the FDY’s signal to the transmitter’s output. 

1. Click the 

Fix Current Low

 button. This should cause 

the FDY to output 4mA. If it is outputting a different 
value, enter the value that the FDY is outputting (in 
mA) into the 

Output Current

 box, then click 

Trim Low

.

2. Check what your multimeter displays as the 
transmitters output. If it is still not precisely 4mA, enter 
it into the 

Output Current 

box again and click

Trim 

Low

 again. Repeat until your multimeter displays an 

acceptable reading.

3. When you are fi nished, click 

Un-Fix Current

. After 

doing this, the output will still be trimmed, but the 
output will no longer be fi xed at 4mA.

4. Continue by clicking the 

Fix Current High

 button. 

This should cause the FDY to output 20mA. If the 
output is a different value, enter it into the 

Output 

Current

 box, then click 

Trim High

.

5. Check what your multimeter displays as the 
transmitters output. If it is still not precisely 20mA, 
enter it into the 

Output Current

 again and click 

Trim 

High

 again. Repeat until your multimeter displays an 

acceptable reading.

6. When you are fi nished, click 

Un-Fix Current

. After 

doing this, the output will still be trimmed, but the 
output will no longer be fi xed at 20mA.

NOTE:

Clicking the RESET button will completely undo output 

trimming.

Loop Test

Use the 

Loop Test

 to trim other instruments in the loop. 

1. To begin the loop test, enter the mA value you want 
the FDY to output to the Loop into the 

Loop Test

 text 

box. Click 

Fix

.

2. Monitor the effect of this on the other instruments in 
the loop, and adjust accordingly.

3. If necessary, repeat steps 1 and 2 and enter a 
different value in the 

Output Current

 box.

4. When you are fi nished, click 

Unfi x

.

 

 

After the trimming parameters have been selected, 
you can continue on by either downloading the 
confi guration or clicking the 

Custom Curve 

tab, and 

proceeding to the 

Programming the Custom Curve 

Parameters

 section.

Содержание FDY

Страница 1: ...FDY FDYNovember 2013 165 730 00E1 PC Programmable Frequency Transmitter and Display PC Programmable Frequency Transmitter and Display...

Страница 2: ...ters 9 Programming the Input Parameters 9 Programming the Range Parameters 10 Programming the Output Parameters 11 Programming the Trimming Parameters 12 Sensor Trimming 12 Output Trimming 13 Loop Tes...

Страница 3: ...eatures a large integral display that shows real time process status About this Manual Wherever you see a Note Caution or WARNING pay particular attention A Note provides information to help you in av...

Страница 4: ...kohms typical 1kHz for input 6V for 0 02 30AC model 125kohms for 10 250AC model Load Capability 508 ohms 24V Output Current Limiting 3 8mA and 21 4mA for input under range and over range 3 6mA and 23...

Страница 5: ...Hz Table 6 Period Input Parameters Resolution 1mV 1mV 1mV Range 0 01 1 5V 0 002 0 15V 0 002 0 15V Hysteresis Measured Period 40 sec to 50sec 40 sec to 2sec 40 sec to 2sec Input Range 100mV 30V DC Reso...

Страница 6: ...3 25 in 62mm 2 45 in 64mm 2 50 in 66mm 2 58 in 76mm 3 00 in 43mm 1 70 in 18mm 0 70 in FDY COM PS 0 PS 0 6027 8 HZ Figure 2 FDY Dimensions 65mm 2 55 in GND GND 1 2 NPT 1 2 NPT 102mm 4 00 in 129mm 5 06...

Страница 7: ...rrent configuration of the attached FDY 4 Measurement Mode The drop down menu selects which type of measurement the FDY will monitor 5 Variables Device Status Communications These sections display the...

Страница 8: ...ion Program 1 2 3 4 5 6 7 Default Factory Configurations The following are the default factory settings for your unit Input Measurement Mode Frequency 0 100Hz Input Hysteresis 10mV Timeout Period 10s...

Страница 9: ...ions Cable Communications Software Programming the FDY All operating parameters of the FDY are set using a PC a serial communication cable and Moore Industries Intelligent PC Configuration software Wh...

Страница 10: ...ed to set this to the default setting of 2V maximum is 2 5V For input voltages below 3V it is recommended to set this to 2 3 of the peak to peak p p input signal voltage plus the low state signal volt...

Страница 11: ...ed reading This can be used to compensate for bent blades in a monitored turbine by setting the value to equal the number of blades on the turbine i e if the turbine has four blades set the Averaging...

Страница 12: ...ox This reduces the effect of sudden spikes and helps stop unnecessary alarms by smoothing the reading Failure Mode Failure Mode lets you set the output of the transmitter when it is malfunctioning It...

Страница 13: ...attempt to trim the FDY ensure that the correct sensor is attached to the transmitter then go to the Trimming tab as shown at the left and 1 Select the User radio button under Trim Mode then answer Y...

Страница 14: ...e output will no longer be fixed at 4mA 4 Continue by clicking the Fix Current High button This should cause the FDY to output 20mA If the output is a different value enter it into the Output Current...

Страница 15: ...int of the transmitter and the transmitter will send out a 4mA signal or the selected output signal if the zero output is set at a value other than 4mA when this point is reached Likewise the point yo...

Страница 16: ...onfiguration program you are ready to download the configuration file Downloading the Configuration File After the configuration has been set to your satisfaction it can be downloaded to the unit by s...

Страница 17: ...signal wiring should be 2 inches Note Some of Moore Industries instruments can be classified as receivers IPT2 IPX2 etc and some can be classified as transmitters TRX TRY etc while some are both a rec...

Страница 18: ...eas requiring intrinsically safe instrumentation Refer to the Special Conditions outlined below before proceeding with installation Special Conditions of Use The following instructions must be adhered...

Страница 19: ...The Interface Solution Experts 19 FDY PC Programmable Frequency Transmitter and Display...

Страница 20: ...isions of the Directive Fulfilled by the Equipment Group II Category 1G EEx ia IIC T4 Notified Body for EC Type Examination LCIE Notified Body Number 0081 33 av du G n ral Leclerc 92260 Fontenay aux R...

Страница 21: ...EC Type Examination Certificate ISSeP 08 ATEX 033 X Technical Standards Used EN 60079 0 2006 Explosive atmospheres Part 0 Equipment General requirements EN 60079 1 2007 Explosive atmospheres Part 1 Eq...

Страница 22: ...IES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVE...

Отзывы: