background image

FDY

10 

The Interface Solution Experts

PC-Programmable Frequency
Transmitter and Display

Figure 7.

  Input Parameters Tab

Programming the Basic Parameters

Programming the Basic Parameters involves selecting 
the desired parameters in the PC Program, then 
downloading those parameters to the FDY. Begin by 
entering the device identifi cation and measurement 
mode parameters into the confi guration software.

Device Identifi cation Information

The 

Tag 

(8 characters, maximum), 

Descriptor

  (16 

characters, maximum) and 

Message

 (32 characters, 

maximum) boxes allow you to assign a unique identity 
to each FDY.

Measurement Mode

Select from Frequency, Period, Pulse Width High, 
Pulse Width Low and Contact Closure. This selects 
the variable to be measured and displayed.  (Unless 
a custom EGU is selected in the Custom Curve tab.)  
(See Figure 5, section 4).

Programming the Input Parameters

When setting input parameters, please read the 
following information for guidance. All input voltages 
above 3V are internally clamped at 3V and all AC 
signals are squared and measured at the zero 
crossing. Therefore the settings for input threshold and 
hysteresis assume a maximum input of 3V.

Use the Input tab in Figure 7 to enter the following 
parameters:

AC / DC Input: 

Select the type of input the FDY will 

measure.

Input Threshold:

  Input threshold is applicable to DC 

inputs only. Input Threshold is the input voltage above 
which the input is considered high. For input voltages 
above 3V, it is recommended to set this to the default 
setting of 2V (maximum is 2.5V). For input voltages 
below 3V, it is recommended to set this to 2/3 of the 
peak-to peak (p-p) input signal voltage plus the low 
state signal voltage.

Input Hysteresis:

 This is the difference between high 

and low voltage points at which the input circuit detects 
changes of input state. For DC inputs this must be less 
than the threshold. For example, if the threshold is set 
for 2V, and the hysteresis is set for 1.2V, the FDY will 
detect high for >2V and low for <0.8V.    

- For DC input voltages above 3V, it is 
recommended to set this to the default setting of 
1.2V (maximum is 1.5V).  
- For DC input voltages below 3V, it is 
recommended to set this to 1/3 of the peak-to peak 
(p-p) input signal voltage plus the low state signal 
voltage.  
- For AC inputs the hysteresis is used to minimise 
noise interference. Above 3V, it is recommended to 
set this to 150mV.
- For AC inputs below 3V, it is recommended to set 
this to 10% of the signal voltage level. 

Timeout Period:

  The number of seconds that the 

input will remain at lower range value before the FDY 
declares a hardware error, if the 

Fail On Input Timeout 

box is checked.  The Timeout Period can be confi gured 
at minimum of 0.5sec to a maximum of 600sec, factory 
default is set to 10sec.

NOTE:

The timeout period must be set greater than the 

Lower Range Value period if Fail On Input Time-out is 

enabled.

Fail On Input Timeout:

  If your input is lower than the 

allowed 

Lower Range Value

 and the 

Fail On Input 

Timeout

 feature is enabled, 

Broken Wire

 (in the 

Device 

Status

 section of the PC Program) or 

Broke Input 

(on 

the FDY display) is declared after the set Timeout 
Period has passed.

Содержание FDY

Страница 1: ...FDY FDYNovember 2013 165 730 00E1 PC Programmable Frequency Transmitter and Display PC Programmable Frequency Transmitter and Display...

Страница 2: ...ters 9 Programming the Input Parameters 9 Programming the Range Parameters 10 Programming the Output Parameters 11 Programming the Trimming Parameters 12 Sensor Trimming 12 Output Trimming 13 Loop Tes...

Страница 3: ...eatures a large integral display that shows real time process status About this Manual Wherever you see a Note Caution or WARNING pay particular attention A Note provides information to help you in av...

Страница 4: ...kohms typical 1kHz for input 6V for 0 02 30AC model 125kohms for 10 250AC model Load Capability 508 ohms 24V Output Current Limiting 3 8mA and 21 4mA for input under range and over range 3 6mA and 23...

Страница 5: ...Hz Table 6 Period Input Parameters Resolution 1mV 1mV 1mV Range 0 01 1 5V 0 002 0 15V 0 002 0 15V Hysteresis Measured Period 40 sec to 50sec 40 sec to 2sec 40 sec to 2sec Input Range 100mV 30V DC Reso...

Страница 6: ...3 25 in 62mm 2 45 in 64mm 2 50 in 66mm 2 58 in 76mm 3 00 in 43mm 1 70 in 18mm 0 70 in FDY COM PS 0 PS 0 6027 8 HZ Figure 2 FDY Dimensions 65mm 2 55 in GND GND 1 2 NPT 1 2 NPT 102mm 4 00 in 129mm 5 06...

Страница 7: ...rrent configuration of the attached FDY 4 Measurement Mode The drop down menu selects which type of measurement the FDY will monitor 5 Variables Device Status Communications These sections display the...

Страница 8: ...ion Program 1 2 3 4 5 6 7 Default Factory Configurations The following are the default factory settings for your unit Input Measurement Mode Frequency 0 100Hz Input Hysteresis 10mV Timeout Period 10s...

Страница 9: ...ions Cable Communications Software Programming the FDY All operating parameters of the FDY are set using a PC a serial communication cable and Moore Industries Intelligent PC Configuration software Wh...

Страница 10: ...ed to set this to the default setting of 2V maximum is 2 5V For input voltages below 3V it is recommended to set this to 2 3 of the peak to peak p p input signal voltage plus the low state signal volt...

Страница 11: ...ed reading This can be used to compensate for bent blades in a monitored turbine by setting the value to equal the number of blades on the turbine i e if the turbine has four blades set the Averaging...

Страница 12: ...ox This reduces the effect of sudden spikes and helps stop unnecessary alarms by smoothing the reading Failure Mode Failure Mode lets you set the output of the transmitter when it is malfunctioning It...

Страница 13: ...attempt to trim the FDY ensure that the correct sensor is attached to the transmitter then go to the Trimming tab as shown at the left and 1 Select the User radio button under Trim Mode then answer Y...

Страница 14: ...e output will no longer be fixed at 4mA 4 Continue by clicking the Fix Current High button This should cause the FDY to output 20mA If the output is a different value enter it into the Output Current...

Страница 15: ...int of the transmitter and the transmitter will send out a 4mA signal or the selected output signal if the zero output is set at a value other than 4mA when this point is reached Likewise the point yo...

Страница 16: ...onfiguration program you are ready to download the configuration file Downloading the Configuration File After the configuration has been set to your satisfaction it can be downloaded to the unit by s...

Страница 17: ...signal wiring should be 2 inches Note Some of Moore Industries instruments can be classified as receivers IPT2 IPX2 etc and some can be classified as transmitters TRX TRY etc while some are both a rec...

Страница 18: ...eas requiring intrinsically safe instrumentation Refer to the Special Conditions outlined below before proceeding with installation Special Conditions of Use The following instructions must be adhered...

Страница 19: ...The Interface Solution Experts 19 FDY PC Programmable Frequency Transmitter and Display...

Страница 20: ...isions of the Directive Fulfilled by the Equipment Group II Category 1G EEx ia IIC T4 Notified Body for EC Type Examination LCIE Notified Body Number 0081 33 av du G n ral Leclerc 92260 Fontenay aux R...

Страница 21: ...EC Type Examination Certificate ISSeP 08 ATEX 033 X Technical Standards Used EN 60079 0 2006 Explosive atmospheres Part 0 Equipment General requirements EN 60079 1 2007 Explosive atmospheres Part 1 Eq...

Страница 22: ...IES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVE...

Отзывы: