FDY
12
The Interface Solution Experts
PC-Programmable Frequency
Transmitter and Display
Figure 9.
Output Parameters Tab
Programming the Output
Parameters
The
Output
section of the PC software is composed
of three sections:
Output Settings, Failure Mode
and
Display Mode
. Use the functions of
Output Settings
to
set the current range from 3.8 to 21.6mA (usually
4-20mA). The minimum span is 4mA.
Output Settings
The output can be reversed (causing the output to
increase as the input decreases) by setting the
Lower
Range Value
in the
Range
tab as higher than the
Upper Range Value
(See Figure 8).
PV
(Primary Variable)
Damping
precisely reads the
input then specifi es an exponential change in the
output by 60% over the time set in the
PV Damping
box. This reduces the effect of sudden spikes and
helps stop unnecessary alarms by smoothing the
reading.
Failure Mode
Failure Mode
lets you set the output of the transmitter
when it is malfunctioning. It will either transmit a 3.6mA
(set to
Fail Low
) or a 23.6mA (set to
Fail High
) signal.
NOTE:
The Failure Mode has no effect unless one of the fail
conditions is active (i.e. Fail On Input Time-out or Over/
Under Range Limits).
Display Mode
Display Mode
selects which variable will be displayed
on the transmitter’s display. Choose between
Primary
Variable, Current, Percentage
and
Display Toggle
.
(Display Toggle switches back and forth from the
primary variable to current and back in one-second
increments). The PC Program’s display is not changed
by changing the selection under the
Display Mode
.
After the
Range
parameters have been selected, you
can continue on by clicking on the
Trimming
tab, and
proceeding to
Programming the Trimming Parameters
.