1-9.
TOOLING SYSTEM SETUP
1-9-1. GENERAL OF SETUP
The Mechanical and Electrical installation must be finished before the Dig Gap Tooling position
control system can be set up. In addition the, hydraulic system must have been flushed for at
least 24 hours.
The Die Gap Tooling position control system setup involves several steps:
1) The Machine setup in the DigiPack
Ⅲ
display (SHIFT
→
F4) must be set to match various
options determined by the blow molding machine and tooling head type.
2) The correct tooling type selection, Convergent or Divergent, must be determined. This
will be determined by which portion of the tooling moves, the die or mandrel, as well as
its internal shape.
3) The DigiPack
Ⅲ
must know if the blow molding machine is a Accumulator or a Continu-
ous molding machine.
4) The working Die Gap end positions, closed and maximum open, must be set.
5) The responsiveness of the Die Gap Tooling position control system is measured and
optimized.
When finished with the Die Gap Tooling system setup, the blow molding machine will be ready to be
programmed for production containers.
The hydraulic pressure must be lowered during the setup procedure or the die gap tooling
may be damaged.
1-9-2. MACHINE SETTING
After confirming the mechanical and electrical connection completely, turn on the DigiPack
Ⅲ
. However,
please do not apply hydraulic pressure yet here.
The LCD of DigiPack
Ⅲ
gets brighter and [F1 Profile] is displayed via the startup screen. Next, press the
[SHIFT] → [F4] key in that order to reflect the machine settings such as language, servo valve type, con-
tinuous type machine or accumulator type machine.
1.9.2.1.
MACHINE SETTINGS (SHIFT
→
F4)
At the DigiPack
Ⅲ
display “SHIFT -> F4” (“Figure 1-34”) is Setting for Machine setting. Set these param-
eters according to Machine type, these parameters should setting before start setting any parameter of
tooling and accumulator. (Accumulator setting only accumulator machine)
The settings required now are:
1) Machine type
- Either Continuous or Accumulator
2) Servovalve type
- Either mechanical feedback, MFB, or electrical feedback, EFB
3) Valve current
- If selected MFB type, this parameter can be selected current level
10, 20, 50 or 100 mA
Depending on the setting of MFB and EFB, the output terminal changes. (The output terminals of
MFB/EFB are located in TB-1.) The Servovalve type that not set is fixed to "0" mA or "0" V, if no
output signal and the actuator does not operate, Please review the machine setting.