01/02 AWB8230-1413GB
Standard form for user defined
parameter settings
169
A054
DC braking torque on deceleration
[%]
0
112
A055
DC braking duration on deceleration
[s]
0.0
112
A056
Behaviour on activation of the DB input
• 00: Starts on activation of the input, ends after
PNU A055
• 01: Runs as long as input is active
–
01
112
A057
DC braking torque on acceleration
[%]
0
112
A058
DC braking duration on acceleration
[s]
0.0
113
A059
DC braking frequency
[kHz]
5.0
113
A061
Maximum operating frequency
[Hz]
0.00
114
A261
Maximum operating frequency (second parameter set)
[Hz]
0.00
114
A062
Minimum operating frequency
[Hz]
0.00
114
A262
Minimum operating frequency (second parameter set)
[Hz]
0.00
114
A063
1. Frequency jump
[Hz]
0.00
114
A064
Jump width of the 1st frequency jump
[Hz]
0.50
114
A065
2. Frequency jump
[Hz]
0.00
114
A066
Jump width of the 2nd frequency jump
[Hz]
0.50
114
A067
3. Frequency jump
[Hz]
0.00
114
A068
Jump width of the 3rd frequency jump
[Hz]
0.50
114
A069
Acceleration pause waiting frequency
[Hz]
0.00
115
A070
Acceleration pause waiting duration
[s]
0.00
115
A071
PID control
• 00: Inactive
• 01: Active
–
00
119
A072
P component of the PID control
–
1.0
120
A073
I component of the PID control
[s]
1.0
120
A074
D component of the PID control
[s]
0.0
120
A075
Setpoint factor of the PID control
[%]
1.00
120
A076
Input actual value signal for PID control
• 00: Input OI
• 01: Input O
–
00
120
A081
AVR function
• 00: Active
• 01: Inactive
• 02: Inactive during deceleration
–
02
128
A082
Motor voltage for AVR function
[V]
230/400
128
A085
Energy-saving mode
• 00: Not active
• 01: Active
–
00
128
A086
Response time in energy-saving mode
[s]
50
128
A092
2. Acceleration time
[s]
15.0
73
A292
2. Acceleration time (second parameter set)
[s]
15.0
73
A093
2. Deceleration time
[s]
15.0
73
A293
2. Deceleration time (second parameter set)
[s]
15.0
73
PNU
Function
Units
WE
Page
Setpoint
efesotomasyon.com - Klockner Moeller - inverter