Programming the Control
Signal Terminals
01/02 AWB8230-1413GB
56
FA3
06
Frequency reached (1)
The FA3 signal is issued when the output frequency lies in the frequency range defined under
PNU C042 and C043 (plus tolerance).
IP
8
Mains failure,
immediate stop
The IP signal is issued on intermittent mains failure.
UV
9
Undervoltage signal
The UV signal is output on undervoltage.
RNT
11
Running time exceeded
The RNT signal is output when the Running time set under PNU b034 is exceeded.
ONT
12
Mains On time exceeded
The ONT signal is output when the Mains On time set under PNU b034 is exceeded.
THM
13
Motor thermal overload
The THM signal is output when the motor overload warning threshold set under PNU C061 is
exceeded.
Signalling relay
2)
K11
–
Signalling relay contacts
During normal fault-free operation, terminals K11K14 are closed. If a malfunction occurs or the
supply voltage is switched off, terminals K11K12 are closed.
Maximum permissible values:
• 250 V ~; Maximum load 2.5 A (purely resistive) or 0.2 A (for a power factor of 0.4)
• 30 V
H
; Maximum load 3.0 A (purely resistive) or 0.7 A (for a power factor of 0.4)
• Minimum required values: Minimum required values: 100 V ~ at a load of 10 mA or 5 V
H
at a
load of 100 mA
K12
K14
1) To activate the function, enter this value in the corresponding parameter.
2) This output can be used as both a signal output and a normal digital output.
Name
Value
1)
Function
Description