Setting Parameters
01/02 AWB8230-1413GB
120
PNU
Function
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
A001
Frequency
setpoint
definition
–
–
00
Definition with the potentiometer on the keypad
01
01
Definition through analog input O (0 to 10 V) or OI
(4 to 20 mA)
02
Definition through PNU F001 and/or PNU A020
A011
Frequency with
minimum
setpoint value
–
j
0 to 400 Hz
Here, the frequency that corresponds to the minimum
voltage setpoint value under PNU A013 is set.
0.0
A012
Frequency with
maximum
setpoint value
–
j
0 to 400 H
z
Here, you can set the frequency that corresponds to the
maximum voltage setpoint value under PNU A014.
0.0
A013
Minimum
setpoint value
–
j
0 to 100 %
The minimum setpoint value entered here relates to the
maximum possible voltage or current setpoint (10 V or
20 mA).
0
A014
Maximum
setpoint value
–
j
0 to 100 %
The maximum setpoint value entered here relates to the
maximum possible voltage or current setpoint (10 V or
20 mA).
100
d004
Actual value
x
factor
j
j
–
Only with active PID control. The factor is set under
PNU A075, from 0.01 to 99.99; default setting: 1.0.
–
F001
Input/display
frequency
value
j
j
0.1 to 400 Hz
Resolution
g
0.1 Hz
The setpoint can be defined using various methods:
• With PNU F001 or A020: Enter the value 02 under
PNU A001.
• Using the potentiometer on the keypad: Enter the value
00 under PNU A001.
• With a 0 to 10 V voltage signal or a 4 to 20 mA current
signal at input terminals O or OI: Enter the value 01 under
PNU A001.
• With the digital inputs configured as FF1 to FF4. After
selection of the required fixed frequency stage using FF1
to FF4, the frequency for the respective stage can be
entered.
The display of the setpoint value is independent of which
method was used to set the setpoint value.
0.0
A072
P component
of the PID
control
j
j
0.2 to 5.0
Adjustment range of the proportional component of the
PID control
1.0
A073
I component of
the PID control
j
j
0 to 3600 s
Adjustment time T
i
of the integral component of the
PID control
1.0
A074
D component
of the PID
control
j
j
0.0 to 100 s
Adjustment time T
d
of the differential component of the
PID control
0.0
A075
Setpoint factor
of the PID
control
–
–
0.01 to 99.99
The display of the frequency setpoint or actual value can be
multiplied by a factor, so that process related quantities
(e.g. flow or similar) can be displayed instead of the
frequency.
1.00
A076
Input actual
value signal for
PID control
–
–
00
Actual value signal present on analog input OI (4 to 20 mA)
00
01
Actual value signal present on analog input O (0 to 10 V)
efesotomasyon.com - Klockner Moeller - inverter