Programming the Control
Signal Terminals
01/02 AWB8230-1413GB
96
Run signal (RUN)
The relay output configured as RUN remains activated as long as
a frequency not equal to 0 Hz is present, i.e. as long as the motor
is driven in a clockwise or anticlockwise direction.
X
Program one of the relay outputs K23-K24 or K33-K34 as RUN
output by entering the value 00 in the corresponding PNU
(C021 or C022) or in PNU C026 for signalling relay contacts
K11-K12.
By default, RUN is assigned to relay output K33-K34.
Figure 91:
Relay output K23-K24 configured as RUN (Run signal)
Figure 92:
Function chart for RUN (Run signal)
f
o
: Output frequency
a
Starting frequency defined with PNU b082
RUN
5...30 V
0
.
250 V
D
K33 K34
FWD/REV
RUN
f
O
a
a
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b082
Increased
starting
frequency
–
j
0.5 to 9.9 Hz
A higher starting frequency results in shorter acceleration
and deceleration times (for example to overcome high
frictional resistance). If the frequencies are too high, fault
message E02 may be issued. Up to the set starting
frequency, the motor accelerates without a ramp function.
0.5