15.6 Control
Inputs
The 3 control inputs (Annexe A) permit the AND- or OR- combination of a channel with
an external switch (i.e. twilight switch). The type of combination is equal for all inputs.
Potential free contact between V+ (Common) and IN 1/2/3.
5
6
7
8
IN 3
IN 2
IN 1
V+
(
C
o
m
m
o
n)
Control inputs ETC 24
MENU
Switch
program
Control
inputs
AND combination: The channel only switches ON, when the control input is active
(closed) AND the switch program shows an ON-, or Signal
command for this time.
OR combination:
The channel switches ON, when the control input is active (closed)
OR the switch program shows an ON-, or Signal command for this
time.
Input configuration:
Function:
Needs to be set to Prog. for using the control input to affect a
channel of the switch program.
State:
Shows the current state of the control input. If the control input is
used for supervision of an external device the input state will be
inhibited (chapter 16).
Channel:
To each control input a channel can be assigned. Channel=00:
Input not assigned.
Al. timeout [s]:
Refer to chapter 16.
C o m b i n a t i o n : A N D
I n p u t 1
I n p u t 2
I n p u t 3
F u n c t i o n : P r o g .
S t a t e : [ O F F ]
C h a n n e l : 0 1
A l . t i m e o u t [ s ] : 0 2
Control inputs ETC 24R