Terminals ETC 14R
Terminal Connection
Description
1 Relay
1
Switching contact 230 VAC / 10 A (cos
= 1)
2 Relay
2
Switching contact 230 VAC / 10 A (cos
= 1)
3 Relay
3
Switching contact 230 VAC / 10 A (cos
= 1)
4 Relay
4
Switching contact 230 VAC / 10 A (cos
= 1)
L
Mains power phase
Mains power input safety connector. (refer to chapter
7.1.1).
Mains power earth
N
Mains power neutral
1
Bat +
Input for running reserve battery (refer to chapter
7.1.4).
2
GND
Ground for battery and DC power supply
3
DC-IN +
Input for external DC power supply (refer to chapter
7.1.2).
4
RS 232 TXD
Interface RS 232 for serial synchronisation in-/output,
file download.
5
RS 232 RXD
6 GND
Ground
7
RS 422 TXD -
Interface RS 422 for serial synchronisation in-/output.
8
RS 422 RXD -
9
RS 422 TXD +
10
RS 422 RXD +
11
DCF input -
DCF input for the connection of a DCF receiver with
current loop output.
12
DCF input +
13
DCF output -
Synthetic DCF output, opto coupler, Umax=30VDC,
I
on
=10..15mA, I
off
=2mA @20VDC
14
DCF
15
DC voltage output 22..29 VDC 200 mA max.
16
Slave clock line 1b
Output of polarised Impulses, DCF or MOBALine
17
Slave clock line 1a
Output of polarised Impulses, DCF or MOBALine